Other problems during message communications, Other problems during message communications -38 – Yaskawa MP3200 Troubleshooting Manual User Manual

Page 113

Advertising
background image

5.2 Troubleshooting Message Communications

Other Problems during Message Communications

5-38

Other Problems during Message Communications

If the problem cannot be resolved with the corrections that are given in Checking the Switch Settings (page
5-13)
to
Communications Stopped during Message Communications (page 5-36), perform troubleshooting
with the following table.

Communications
Function Module

Error

Cause

Correction

218IFD

In a configuration
where the remote sta-
tion is the master sta-
tion and the local
station is the slave sta-
tion, the remote station
cannot write to certain
register addresses in
the Machine Controller.

There are errors in the follow-
ing parameter settings of the
MSG-RCVE function.
• PARAM36 and PARAM37

(M writing range lower limit)

• PARAM38 and PARAM39

(M writing range upper limit)

• PARAM40 and PARAM41

(G writing range lower limit)

• PARAM42 and PARAM43

(G writing range upper limit)

• PARAM44 and PARAM45

(O writing range lower limit)

• PARAM46 and PARAM47

(O writing range upper limit)

Correct the parameter settings of
the MSG-RCVE function where
the errors exist.
Refer to the following manual for
details on the parameters of the
MSG-RCVE function.

MP3000 Series Communica-
tions User’s Manual
(Manual
No.: SIEP C880725 12)

In a configuration
where the local station
is the master station
and the remote station
is the slave station, the
Machine Controller
cannot read or write
from/to certain register
addresses in the remote
station.

An attempt has been made to
access special registers or
memory-protected registers in
the remote station.

Check the specifications of the
device that is used as the remote
station.

The addresses of the
registers to read/write
from the local station to
the remote station and
those of the registers to
read/write from the
remote station to the
local station are incon-
sistent.

There are errors in the follow-
ing parameter settings of the
MSG-RCVE function.
• PARAM20 and PARAM21

(coil offset)

• PARAM22 and PARAM23

(input relay offset)

• PARAM24 and PARAM25

(input register offset)

• PARAM26 and PARAM27

(hold register offset)

• PARAM28 and PARAM29

(data relay offset)

• PARAM30 and PARAM31

(data register offset)

• PARAM32 and PARAM33

(output coil offset)

• PARAM34 and PARAM35

(output register offset)

Correct the parameter settings of
the MSG-RCVE function where
the errors exist.
Refer to the following manual for
details on the parameters of the
MSG-RCVE function.

MP3000 Series Communica-
tions User’s Manual
(Manual
No.: SIEP C880725 12)

Continued on next page.