5.2 Troubleshooting Message Communications

Other Problems during Message Communications

5-39

T

roubleshooting Programming and Debugging

218IFD

I/O message communi-
cations do not start.

There are no slave settings
(message receive settings and
instructions) at the remote sta-
tion.

Make the necessary slave settings
(message receive settings and
instructions) at the remote sta-
tion.
(I/O message communications
can be used to execute the Send
Message function without a lad-
der program. Two connections
are used to read and write regis-
ters. Two connections are used to
read and write registers. For this
reason, receive settings (mes-
sage receive settings and instruc-
tions) for two connections are
required at the remote station.)

Continued from previous page.

Communications

Function Module

Error

Cause

Correction