2.2 CPU Unit/CPU Module Indicators and Display

MECHATROLINK-III Status Indicators

2-16

MECHATROLINK-III Status Indicators

These indicators show the status of the MECHATROLINK-III communications.

If the LK1 or LK2 status indicator is not lit, there may be an error in the communications with MECHA-
TROLINK-III.

Indicator

Name

Color

Indicator

Status

Description

CN

Green

Lit.

MECHATROLINK-III communications is established with
the CPU Unit as a slave (i.e., the Connect command is ON).

Not lit.

The connection has not been established.

LK1

Green

Lit.

MECHATROLINK-III communications are active on port 1.

Not lit.

No MECHATROLINK-III communications are connected
on port 1.

LK2

Green

Lit.

MECHATROLINK-III communications are active on port 2.

Not lit.

No MECHATROLINK-III communications are connected
on port 2.

LK1 and LK2

Status

Indicators

Cause

Correction

Not lit.

The MECHATROLINK-III cable
is not connected properly.

Remove the MECHATROLINK-III cable and insert it into
the MECHATROLINK-III connector again.

The MECHATROLINK-III cable
has a broken wire.

Replace the MECHATROLINK-III cable.