Servopack status monitor (iw2c) table, Servopack alarm code (iw2d) tables – Yaskawa MP3200 Troubleshooting Manual User Manual

Page 71

Advertising
background image

4.2 Troubleshooting Motion Errors

Checking Status and Alarms of a Reference-type SERVOPACK with MECHATROLINK-III Communications

4-21

T

roubleshooting Communications and Motion Control

Checking Status and Alarms of a Reference-type SERVOPACK
with MECHATROLINK-III Communications

Use the MPE720 to check the status and alarms of a Reference-type SERVOPACK with MECHA-
TROLINK-III Communications.

This section gives the items that can be checked in the SERVOPACK status and alarm information.

SERVOPACK Status Monitor (IW2C) Table

The status of a Reference-type SERVOPACK with MECHATROLINK-III Communications can be moni-
tored in the SERVOPACK Status Monitor parameter (IW2C).

SERVOPACK Alarm Code (IW2D) Tables

If bit 0 (SERVOPACK Error) in IL04 (Alarms) is ON, an alarm has occurred in the Reference-type
SERVOPACK with MECHATROLINK-III Communications. If bit 0 (SERVOPACK Error) in IL04
(Alarms) is ON, an alarm has occurred in the SERVOPACK with MECHATROLINK Communications.
You can check the specific alarm in IW2D (SERVOPACK Alarm Code).
The alarm codes are listed in the following tables. Refer to the relevant SERVOPACK manual for correc-
tive measures.

Bit

Status

Meaning

Bit 0

Drive Alarm
(D_ALM)

0: No drive alarm.
1: Drive alarm occurred.

Bit 1

Drive Warning
(D_WAR)

0: No drive warning.
1: Drive warning occurred.

Bit 2

Command Ready
(CMDRDY)

0: Commands cannot be received.
1: Commands can be received.

Bit 3

Alarm Clear Execu-
tion Completed
(ALM_CLR_CMP)

0: Servo OFF (base lock)
1: Servo ON (no base lock)

Bit 6 and Bit 7

Echo-back of Com-
mand ID (RCMD_ID)

This parameter reports the echo-back value of the command ID of a
MECHATROLINK-III command.

Bit 8 to Bit B

Command Error
(CMD_ALM)

This parameter reports the alarm status of a MECHATROLINK-III
command.

Bit C to Bit F

Communications Error
(COMM_ALM)

This parameter reports the communications alarm status of a MECHA-
TROLINK-III command.

Advertising