7.5 System Register Configuration and Error Status

Alarm History Information

7-71

T

roubleshooting System Errors

Details

The registers for the alarm history entries are structured as shown below. This example shows the system
register addresses for alarm history entry 1.

Alarm Details

Alarm details are given based on the alarm details format type.

• When the Alarm Details Format Type Is 1 (Operation Error)

Register Address

Remarks

Register Address

Example

SW + 0

SW16203

SW + 1

Alarm Code

SW16204

SW + 2

Alarm Details Format Type
1: Operation error
2: I/O error
3: Other error

SW16205

SW + 3

Year when alarm occurred

SW16206

SW + 4

Month when alarm occurred

SW16207

SW + 5

Day when alarm occurred

SW16208

SW + 6

Hour when alarm occurred

SW16209

SW + 7

Minutes when alarm occurred

SW16210

SW + 8

Seconds when alarm occurred

SW16211

SW + 9

Alarm details
The information depends on the alarm details format type.

Alarm Details (page 7-71)

SW16212

SW + 10

SW16213

SW + 11

SW16214

SW + 12

SW16215

SW + 13

SW16216

SW + 14

Reserved for system.

SW16217

SW + 15

Reserved for system.

SW16218

Register Address

Remarks

Register Address

Example

SW + 9

Error Drawing No.

SW16212

SW + 10

Calling Drawing No.

SW16213

SW + 11

Calling Drawing Step No.

SW16214

SW + 12

Reserved for system.

SW16215

SW + 13

Reserved for system.

SW16216

 hex

01 to 09: Gives the slot number where the Module

in which the alarm occurred is mounted.

1 to 4: Gives the unit number of the Module in

which the alarm occurred is mounted.

1 to 7: Gives the Rack number where the Module in

which the alarm occurred is mounted.