NTAK79 2.0 Mb PRI card

The connection to the echo canceler/test port is available at the
backplane/MDF connector. The signals at this port conform to the EIA
RS-232C standard.

Clock controller interface

The clock controller circuitry on the NTAK79 is identical to that of the
NTAK20 clock controller.

Though several DTI/PRI packs can exist in one system, only one clock
controller may be activated. All other DTI/PRI clock controllers must be
switched off.

clock controller circuitry on the NTAK79 is identical to that of the NTAK20
clock controller.

Note that while several DTI/PRI packs may exist in one system, only one
clock controller may be activated (all other DTI/PRI clock controllers must
be switched off).

The clock controller circuitry on the NTAK79 is identical to that of the
NTAK20 clock controller.

Though several DTI/PRI packs can exist in one system, only one clock
controller may be activated. All other DTI/PRI clock controllers must be
switched off.

Clocking modes

The clock controller can operate in one of two modes:

tracking

non-tracking (also known as free-run)

The clock controller can operate in one of two modes: tracking or
non-tracking (also known as free-run).

The clock controller can operate in one of two modes:

tracking

non-tracking (also known as free-run)

For more information on clocking modes, see

"180" (page 126)

.

Tracking mode

There are two stages to clock controller tracking:

tracking a reference, and

locked onto a reference.