Nt8d14 universal trunk card – Nortel Networks 1000 User Manual

Page 90

Advertising
background image

90

Option settings

Table 27
NT6D80 Multi-purpose Serial Data Link card (cont’d.)

RS-232-D DTE or DCE*
RS-422-A DTE
RS-422-A DCE

all off
all off
all on

all off
all on
all off

* RS-232-D DTE and DCE modes are software configured. RS-422-A DTE and DEC modes are
switch configured.

Note: The device number for the MSDL card is configured in LD17 at the prompt DNUM. You must
also set the device number, using switches S9 and S10, on the MSDL card. S9 designates ones
and S10 designates tens. To set the device number as 14, for example, set S10 to 1 and S9 to 4.

NT8D14 Universal Trunk card

Table 28 "NT8D14 vintage AA jumper strap settings" (page 90)

through

Table 32 "NT8D14 vintages BA/BB cable loop resistance and loss" (page
92)

list option settings for the NT8D14 Universal Trunk card.

Table 28
NT8D14 vintage AA jumper strap settings

Modes

Location

Jumper strap

Central Office (CO)

J1, J2

off

2-way tie trunk (loop dial repeat)

J1, J2

off

2-way tie trunk (outgoing/incoming dial)

J1, J2

off

Recorded announcement (RAN)

J1, J2

off

Paging trunk

J1, J2

off

Japan CO/DID operation

J1, J2

off

DID operation: loop length > = 2000

3

/

4

J1, J2

on

DID operation: loop length < 2000

3

/

4

J1, J2

off

Note 1: off = no strap present.

Note 2: Locations (J1, J2) apply to all eight units.

Table 29
NT8D14 vintages BA/BB jumper strap settings-factory standard

Jumper strap settings

Trunk types

Loop length

J1.X

J2.X

J3.X

J4.X

CO/FX/WATS

2-way tie (LDR)

2-way tie (OAID)

Zero–1524 m (5000 ft)

DID

Zero–600 ohms

Off

Off

1–2

1–2

Nortel Communication Server 1000

Circuit Card Reference

NN43001-311

02.06

Standard

27 August 2008

Copyright © 2003-2008 Nortel Networks

.