CHAPTER 2: INSTALL ATION/CONFIGURATION

2.80

EP OS MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL

 

 

For EntelliPro ES3 types:

Input 99 is mapped to contactor 1 feedback

- active high

Input 98 is mapped to contactor 2 feedback

- active low

Input 97 is mapped to limit switch 1 reached

- active low

Input 96 is mapped to limit switch 2 reached

- active low

Input 95 is mapped to emergency stop

- active low

Input 94 is mapped to main circuit feedback

- active high

Input 93 is mapped to safety circuit

- active low


Output 41 is mapped to contactor 1
Output 43 is mapped to contactor 2
Output 45 is mapped to failure


For EntelliPro ES5 types:

Input 99 is mapped to contactor 1 feedback

- active high

Input 98 is mapped to contactor 2 feedback

- active high

Input 97 is mapped to external supervision 1

- active high

Input 96 is mapped to mode switch local

- active high

Input 95 is mapped to mode switch remote

- active high

Input 94 is mapped to main circuit feedback

- active low

Input 93 is mapped to control circuit feedback

- active low

Input 11 is mapped to command OFF

- active low

Input 12 is mapped to command ON1

- active high

Input 13 is mapped to command ON2

- active high

Input 14 is mapped to torque switch 1 feedback

- active low

Input 15 is mapped to torque switch 2 feedback

- active low

Input 16 is mapped to emergency stop

- active low

Input 17 is mapped to safety circuit

- active low

Input 18 is mapped to limit switch 1 feedback

- active low

Input 19 is mapped to limit switch 2 feedback

- active low


Output 41 is mapped to contactor 1
Output 43 is mapped to contactor 2
Output 45 is mapped to ATEX redundancy contactor
Output 22 is mapped to local control
Output 23 is mapped to ON1 – relay flashing
Output 24 is mapped to ON2 – relay flashing
Output 25 is mapped to drawer ready switch (high priority) and identification – relay flashing (low priority)
Output 26 is mapped to failure

NOTE:

If default configuration box is left un-checked, the user will have the ability to change the mapping and other

parameters.