CHAPTER 2: INSTALL ATION/CONFIGURATION

2.48

EP OS MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL

 

 

For EntelliPro ES3 types:

Input 99 is mapped to forward contactor 1 feedback

- active high

Input 98 is mapped to reverse contactor 2 feedback

- active low

Input 97 is mapped to by-pass contactor feedback

- active high

Input 96 is mapped to up-to-speed feedback

- active high

Input 95 is mapped to emergency circuit

- active low

Input 94 is mapped to starter fault

- active low

Input 93 is mapped to safety circuit

- active low

Output 41 is mapped to forward contactor 1

Output 43 is mapped by-pass contactor

Output 45 is mapped to reverse contactor 2

For EntelliPro ES5 types:

Input 99 is mapped to forward contactor 1 feedback

- active high

Input 98 is mapped to reverse contactor 2 feedback

- active high

Input 97 is mapped to by-pass contactor feedback

- active high

Input 96 is mapped to up-to-speed feedback

- active high

Input 95 is mapped to starter fault feedback

- active low

Input 94 is mapped to main circuit feedback

- active low

Input 93 is mapped to control circuit feedback

- active low

Input 11 is mapped to command OFF

- active low

Input 12 is mapped to command forward ON1

- active high

Input 13 is mapped to command reverse ON2

- active high

Input 14 is mapped to external fault 1

- active high

Input 15 is mapped to external fault 2

- active low

Input 16 is mapped to emergency stop

- active low

Input 17 is mapped to safety circuit

- active low

Input 18 is mapped to mode switch local

- active high

Input 19 is mapped to mode switch remote

- active high

Output 41 is mapped to forward contactor 1

Output 43 is mapped to reverse contactor 2

Output 45 is mapped to by-pass contactor

Output 22 is mapped to ATEX redundancy contactor

Output 23 is mapped to ON1/ON2 command (start)

Output 24 is mapped to reset

Output 25 is mapped to drawer ready switch (high priority) and identification –relay flashing (low priority)

Output 26 is mapped to failure