GE Industrial Solutions EntelliPro ES User Manual

Page 184

Advertising
background image

CHAPTER 4: COMMUNICATION

EP OS MOTOR MANAGEMENT SY STEM – INSTRUCTION MANUAL

4.47

 

 

 

 

 

Size

Telegram Name

Description

Default

Bytes

2 * 8-bit

5

 

 

 

 
 

 

 

6

Reset Device Errors

BIT0 - Reserved
BIT1 - Reserved

BIT2 - Reset Parameter Error

BIT3 - Reset Watchdog Error

BIT4 - Reset Timer Interrupt Error

BIT5 - Reserved

BIT6 - Reset EEPROM Error

BIT7 - Reserved

 

BIT0 - Reset Start Attempt

BIT1 - Reset Thermistor Hardwire Error

BIT2- BIT7 - Reserved

Reset Device Errors

1 will reset the specific error

 

2

8-bit

RESET Firmware

BIT0 - Reset operation hours (motor)

BIT1 - Reset switching cycle counter (motor)
BIT2 - Reserved

BIT3 - Reset Maximum Current
BIT4 - Reset Minimum Current
BIT5 - Reset time stamp

BIT6 - Reset Overload memory

BIT7 - Clear Analog Value Log

Reset Firmware Parameters

 

 
 

 

 

 

This command is required to re-start the log

 

1

8-bit

FIRMWARERESET_1

BIT0 - Stop Analog Logging

BIT1 - Reset Contactors 41 Operations Counter
BIT2 - Reset Contactors 42 Operations Counter
BIT3 - Reset Contactors 43 Operations Counter
BIT4 - Reset Contactors 4 Operations Counter
BIT5 - Reset Thermistor trips Counter

BIT6 - Reset Ground Fault Sum Trip Counter

BIT7 - Reset Hours of non-operation (Motor stopped

hours)

 

 

1

 

B2702

Set Value Telegram

 

6

16-bit

Parameter Select

1- Operation Hours

2- Switch Counter

3- Reserved

4- Reserved

5- Reserved

6- Reserved

7- Reserved

 

Added for ESS-DP V5

8 - Contactors 1 Operations Counter

9 - Contactors 2 Operations Counter

10 - Contactors 3 Operations Counter

11 - Contactors 4 Operations Counter

12 - Thermal Overload trips Counter (2-bytes only)

13 - Thermistor trips Counter (2-bytes only)

14 - Ground Fault Sum Trip Counter (2-bytes only)

15 - Hours of non-operation (Motor stopped hours)

 

Set the Operation Hours

Set the Switch Counter (for which contactor)

 

2

32-bit

Set Value

Set value to the specific parameter selected

 

4

Advertising