CHAPTER 2: INSTALL ATION/CONFIGURATION

2.4

EP OS MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL

 

 

EN

50022

D

 

 

2.1.1.3 Mounting

 

CAUTION:

To avoid the potential for personal injury from fire hazards, ensure the unit is mounted in a safe

location and/or within an appropriate enclosure. Unit must be un-powered and all connectors removed
during installation.

 

 

The EntelliPro ES can be DIN mounted using DIN rail to the equipment . The DIN rail mounting, removal, wire
connection and connector insertion and removal are illustrated in Figure 2-3.

 

Steps for installation and removal:

A. Secure DIN Rail (see Item A) to the panel with an appropriate fastener.

 

B. To insert the unit , snap the EntelliPro ES to the Din rail while releasing the pressure on the unit

mounting tabs (see Item B). To remove lift the unit out while holding the tabs up with a
screwdriver or another appropriate tool.

 

C. To insert the connector simply push the connecter toward the EntelliPro terminal (see Item

C). Ensure you have the appropriate connector. To remove, separate the connector from the
housing using the tip of a small screwdriver (see Item C) or other appropriate tool.

 

D. Insert each wire into the connector (see Item D) and tighten the connection using the torque

shown in the figure. Lightly pull on the wire to check the connection.

 

E. Use a small screwdriver or other appropriate tool to adjust the Modbus and Profibus

communication address switch (see Item E).

 

 

 
 

 
 

 

1 x 2,5mm²

AWG...

 

 

 

 

C

 

 

 

119-111 99-91

EntelliPro ES

9

 

 
 

 

 

 
 

4

4

2

6 2

6

0

0

8

D

10

 

 

 

E

 

A

72-71

COM

RUN

12

Address

 

G = default Address

 

11-19 21-26

31-39 41-46

51-57 61-67

C

 

 

B

B

 
 

 
 

 

Figure 2-3: EntelliPro ES DIN rail mounting and removal