CHAPTER 3: MOTOR PR OTECTION

EP OS MOTOR MANAGEMENT SY STEM – INSTRUCTION MANUAL

3.23

 

 

 

3.5 Undercurrent protection

 

The undercurrent function switches off the motor during an undercurrent condition.

Under current threshold is set in WinESG parameterization/device settings panel shown in the illustration below or
Modbus function code 06 register 20. The under current threshold is settable from 1 to 100% of motor load (Ir),

If a current falls below the under current threshold for a pre-defined timer set in WinESG parameterization/timer panel
shown in the illustration below or Modbus function code 06 register 40 a failure or warning will be generated depending
o

n the alarm setting. The over current time is settable from 0.1 to 6553.5 seconds.

 