1 entellipro cp3 main panel – GE Industrial Solutions EntelliPro ES User Manual

Page 238

Advertising
background image

If “Communication Error” appears

in the message box, there is no communication to the EntelliPro ES.

When a communication error is reported, check for missing cable connections and appropriate Modbus address settings.

See

section 6.2 for additional settings information.

2 : Valve 1

local
operate

Drawer ready

COM 1

Communication Error

COM1: Connection 1

No Modbus communication to

the connected EntelliPro ES.

Message box appears cyclically

EPOS MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL

6.3

CHAPTER 6: ENTELLIPRO CP3 and CP5 APPLICATION