Size

Telegram Name

Description

Default

Bytes

Unit

Scale

2

BIT0 - Safety circuitStatus

 

BIT1 - EntelliPro Local Mode Status

BIT2- EntelliPro Remote Mode Status

BIT3 - Drawer Operation Mode Status

 

 

BIT4- Drawer Test Mode Status

 

 

BIT5 - Limit Switch1 Status

 

BIT6 - Limit Switch2 Status

 

BIT7- General Device Error Status

1 indicates that safety circuit input is set. Input must be mapped.

 

1 indicates that switch position is set to local. If hardwire is
contrlling the switch then digital input must be mapped.

 

1 indicates that Switch position is set to remote. Input must be

mapped.

 

1 indicates that drawer is in operation mode. Input must be
mapped.

Also configurion telegram B40001 43 bit 3 -

ActivateDrawerPositionSupervision must be set.

 

1 indicates that drawer is in test mode. Input must be mapped

ActivateDrawerPositionSupervision must be set.

 

1 indicates that limit switch 1 is set.

 

1Indicates that limit switch2 is set.

 

1 indicates there is a general device error.

 

 

 

 

3

BIT0 - Feedback_IdentificationStatus

 

 

BIT1 - Class1Failure

 

BIT2 - ModbusFailure

 

BIT3 - ByPassSwitchedON

BIT4 - Switching1Progress

 

BIT5 - Switching2Progress

 

 

BIT6 - Breaker Tripped 2

 

BIT7 -Status Charged

1 indicates the feedback from identification command - output
must be mapped optional as soon as the ID command is issued

this bit is set.

 

1 indicates Profibus Class1 failure

 

1 indicates Modbus failure

 

1 indicates by-pass switch on. Input must be mapped.

 

1 indicates switching is progress. Input must be mapped as well as
the corresponding output.

 

1 indicates switching is progress. Input must be mapped as well as

the corresponding output.

 

1 indicates Breaker tripped. Input must be mapped.

 

1 indicates status charge. Input must be mapped.

 

 

 

 

4

BIT0 - TorqueSwitching1Progress

 

 

BIT1 - TorqueSwitching2Progress

 

 

BIT2 -Start Phase

 

BIT3 -RunPhase

 

BIT4 - ThermistorLineBroken

BIT5-ThermistorLineShorted

BIT6 - Free

BIT7 - Free

1 indicates torque switching is in progress. Input must be mapped
as well as the corresponding output.

 

1 indicates torque switching is in progress. Input must be mapped

as well as the corresponding output.

 

1 indicates the motor is in the start phase.

 

1 indicates that the morot is in the run phase.

 

1 indicates thermistor line open.

 

1 indicates thermistor line shorted.

 

 

 

 

Advertising