CHAPTER 5: WinESG

EP OS MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL

5.

20

 

 

5.3.2.5 Parameterization Timer panel

Timer panel – The timer panel provide

s a means for setting the 16 timers available on EntelliPro ES. The timers can be

adjusted within the range of 0.1 to 6553.5 seconds.

Refer to Figure 5-11 for the WinESG parameterization timer panel.

Figure 5-11-: WinESG parameterization timer panel

Contactor feedback time:

fault or warning is indicated if contactor feedback (current or
contactor) is not received within this time.

Motor start time:

fault or warning is indicated if a current is above the start phase
threshold for the set amount of time.

Modbus failure OFF/ON delay time:

fault or warning is indicated if a Modbus failure exists after this
time expires. Modbus timeout time must be set in Modbus
register 59.

Current feedback time:

fault or warning is indicated if a current is below 0.2 * Ir for the
set amount of time after a start.

Motor ON direction switch over time:

use mainly on two-speed motor. Transition from one speed to
the other will only occur after this time expires.

Class 1 failure OFF/ON delay time:

fault or warning is indicated if a Profibus class 1 failure exist

s after

this time expires.

Over current delay time:

fault or warning is indicated if a current is above over current
threshold for the set amount of time.