EP OS MOTOR MANAGEMENT SY STEM – INSTRUCTION MANUAL

CHAPTER 5: WinESG

5.2

3

 

 

Local / Remote selection switch in illustration B allows the setting of a source that controls the local-remote switch

Switch selection control:

The following sources can be selected: Class 1, Modbus, Hardwire,

Fixed local, or Fixed Remote. The selected source determines if

local or remote sources control the motor operation (ON/OFF).

Refer to section 2.2.1 for additional information.


If Bus failure supervision for the specific protocol in illustration C, is selected the bus failure behavior can be defined.
Bus failure behavior indicates the reaction of EntelliPro ES in case of communication failure.

Ignore:

contactor stays ON or OFF if bus failure appears.

Delayed OFF:

contactor switches OFF after a specific time delay set on Modbus

failure OFF/ON delay timer and/or Class 1 failure OFF/ON delay

time.

Delayed ON1:

ON1 command is issued after a specific time delay set on Modbus

failure OFF/ON delay time and/or Class 1 failure OFF/ON delay

time. Use on two-speed motor.

Delayed ON2:

ON2 command is issued after a specific time delay set on Modbus

failure OFF/ON delay time and/or Class 1 failure OFF/ON delay

time. Use on two-speed motor.


5.3.2.8 Parameterization Typical settings panel

The typical setting panel provides a means for the activation and deactivation of the ATEX

, thermistor line broken or

short, feedback via current or contact, and other settings related to the typical operation. Refer to figure 5-14 for the
WinESG parameterization typical settings panel.

Figure 5-14: WinESG parameterization typical setting panel