CHAPTER 4: COMMUNICATION

EP OS MOTOR MANAGEMENT SY STEM – INSTRUCTION MANUAL

4.39

 

 

 

 

 

Size

Telegram Name

Description

Default

Bytes

Unit

Scale

8-bit * 12

8-bit

8-bit

8-bit

8-bit

8-bit

8-bit

8-bit

8-bit

8-bit

8-bit

8-bit

8-bit

Serial number

Serial Number

dependent

12

format - 1

 

 

4 * 8-bit

B20008

Status Telegram

74

 

 

1

 

BIT0 - Contactor1 Feedback Status

BIT1 - Contactor2 Feedback Status

BIT2 - Parameter Mode Status

BIT3 - Switch Protected Status

 

 
 

 
 
 

BIT4 - Start Attempt Status

BIT5 - Drawer Ready Status

BIT6 - General Warning Status

 

BIT7 - General Fault Status

 

1 indicates that contactor1 feedback input is received. Note that
the input must be mapped - refer telegram B40001

 

1 indicates that contactor2 feedback input is received. Note that
the input must be mapped

.

 

1 indicates that parameterization is allowed. This must be enabled

to change telegram B2736 -46 bit 3/4:

 

1 indicates:

OFF command is received by the Remote source when switch

is in LOCAL position, motor cannot be turned ON from the local
source again till this bit cleared - set to zero

Provided block Local switch ON feature is actiavted - can be

activated on configuration

telegram (40001 43 bit6 must be set)

 

1 indicates the Start attempts has exceeded the parmeterized
count

.

 

1 indicates that the motor is ready to start (must be 1 for motor to

start )

 

1 indicates there is a general warning. Telegram B30264
provides additional warning details. To reset warning refer to
write telegram B

 

1 indicates there is a general failure. Telegram B30008 provides

additional details.

 

Configuration

4

dependent

 

 

(Format 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12)

3

6

7

9

12

11

10

8

4
5

2