Motor Starter Standard Configuration

EntelliPro ES3

 

Full-voltage

non-

reversing

Full-voltage

reversing

Star-delta

non-

reversing

Star-delta

reversing

Softstarter

Softstarter

reversing

Breaker

Dahlander

Pole-

changer

 

Actuator

Solenoid

valve

Input 97 Mapping

Control

Circuit

Feedback

Control

Circuit

Feedback

Contactor 3

Feedback

N/A

Bypass

Feedback

Bypass

Feedback

Breaker

Charged

Contactor 3

Feedback

Control

Circuit

Feedback

Limit Open

Feedback

Limit Open

Feedback

Input 97 High/low Activation

Active Low

Active Low

Active High

N/A

Active High

Active High

Active High

Active High

Active Low

Active Low

Active Low

Input 96 Mapping

Main Circuit

Feedback

Main Circuit

Feedback

Main Circuit

feedback

N/A

Up to Speed

Feedback

Up to Speed

Feedback

Main Circuit

Feedback

Main Circuit

Feedback

Main Circuit

Feedback

Limit Close

Feedback

Limit Close

Feedback

Input 96 High/low Activation

Active Low

Active Low

Active Low

N/A

Active High

Active High

Active Low

Active Low

Active Low

Active Low

Active Low

Input 95 Mapping

Emergency

Stop

Emergency

Stop

Emergency

Stop

N/A

Emergency

Stop

Emergency

Stop

Breaker

Tripped 2

Emergency

Stop

Emergency

Stop

Emergency

Stop

Emergency

Stop

Input 95 High/low Activation

Active Low

Active Low

Active Low

N/A

Active Low

Active Low

Active Low

Active Low

Active Low

Active Low

Active Low

Input 94 Mapping

External

Supervision

External

Supervision

External

Supervision

N/A

Starter Fault

Feedback

Starter Fault

Feedback

Tripped

External

Supervision

External

Supervision

External

Supervision

External

Supervision

Input 94 High/low Activation

Active High

Active High

Active High

N/A

Active Low

Active Low

Active Low

Active High

Active High

Active Low

Active High

Input 93 Mapping

Safety

Circuit

Safety

Circuit

Safety

Circuit

N/A

Safety

Circuit

Safety

Circuit

Safety

Circuit

Safety

Circuit

Safety

Circuit

Safety

Circuit

Safety

Circuit

Input 93 High/low Activation

Active Low

Active Low

Active Low

N/A

Active Low

Active Low

Active Low

Active Low

Active Low

Active Low

Active Low

Relay Output Mapping

 

 

 

 

 

First Function Relay 42 Mapping

Contactor 1

Contactor 1

Contactor 1

N/A

Contactor 1

Contactor 1

MCCB on

Contactor 1

Contactor 1

Contactor 1

Contactor 1

Second Function Relay 42 Mapping

None

None

None

N/A

None

None

None

None

None

None

None

First Function Relay 43 Mapping

ON 1

Feedback

Contactor 2

Contactor D

N/A

Bypass

Bypass

MCCB off

Contactor 2

Contactor 2

Contactor 2

ON 1

Feedback

Second Function Relay 43 Mapping

None

None

None

N/A

None

None

None

None

None

None

None

First Function Relay 45 Mapping

Failure

Failure

Contactor Y

N/A

Reset

Left

Reset

Contactor Y

Failure

Failure

Failure

Second Function Relay 45 Mapping

None

None

None

N/A

None

None

None

None

None

None

None

First Function Relay 22 Mapping

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

Second Function Relay 22 Mapping

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

First Function Relay 23 Mapping

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

Second Function Relay 23 Mapping

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

First Function Relay 24 Mapping

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

Second Function Relay 24 Mapping

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

First Function Relay 25 Mapping

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

Second Function Relay 25 Mapping

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

First Function Relay 26 Mapping

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

Second Function Relay 26 Mapping

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

 

Table 2-6: EntelliPro ES3 Motor Starter Configuration