CHAPTER 5: WinESG

EP OS MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL

5.1

8

 

 

5.3.2.3 Parameterization Alarms panel

The alarm panel provides a means to enable and disable protections, set protections and inputs as fault or warning,
and set the number of allowable auto resets after an overload trip. Refer to Figure 5-9 for the WinESG
parameterization alarms panel.

Figure 5-

9: WinESG parameterization alarm panel

Warning:

when active, a specific fault will not open the motor contactor. A
warning will be provided on the control screen.

Manual reset:

fault or warning will require a manual reset. The reset can be done
via Modbus function code 5 registers 65 to 106, Profibus class 1
telegram B2701 or WinESG control panel.

Overload auto reset:

number of auto-reset allowed after an overload fault. This
number is reset after 1 hour without overload failure

NOTE:

For proper operation of Contactor/Current feedback either Feedback via contact activated or Feedback via

current activated in the WinESG parameterization/Typical settings panel must be set. Refer to the illustration below.

CAUTION:

For protecting motors in explosive areas, only the values n = 0, 1, 2, 3 are allowed.