The following table shows the command that can be initiated using function code 05.

 

 

 

Operation Code

Description

 

1

Contactor1 ON

2

Contactor2 ON

5

Contactors 1 & 2 OFF

6

Module Identification (request EntelliPro ES ID)

9

1

Lock Switch Command

10

Switch to Local mode

11

Switch to Reset mode

65

Reset Overload Failure

66

Reset Phase Loss Failure

67

Reset Ground Fault Failure

68

Reset Unbalanced Load Failure

69

Reset Thermistor Failure

70

Reset Emergency stop Failure

71

Reset Limit Switch Failure

72

Reset Safety Circuit Failure

73

Reset Main Circuit Failure

74

Reset Control Circuit Failure

75

Reset Switch Position Failure

76

Reset Under Load Current Failure

77

Reset Overload Current Failure

78

Reset External Supervision Failure

79

Reset Long Start Failure

80

Reset Typical Specific Failure

81

Reset Overload Warning

82

Reset Phase Loss Warning

83

Reset Ground Fault Warning

84

Reset Unbalanced Load Warning

85

Reset Thermistor Warning

86

Reset Emergency stop Warning

87

Reset Limit Switch Warning

88

Reset Safety Circuit Warning

89

Reset Main Circuit Warning

90

Reset Control Circuit Warning

91

Reset Contactor Feedback Warning

92

Reset Under Load Current Warning

Advertising