EP OS MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL

CHAPTER 4: COMMUNICATION

 

 

 

 

 

Input

Register

Address

Data

Size

 

Parameter Name

Units

Scale

Format

Note

89

(cont.)

16 bit

133 = Emergency Stop Fault Reset

134 = Limit Switch Fault Reset

135 = Safety Circuit Fault Reset

136 = Main Circuit Fault Reset

137 = Control Circuit Fault Reset

138 = Switch Position Fault Reset

139 = Underload Current Fault Reset

140 = Overload Current Fault Reset

141 = External Supervision Fault Reset

142 = Long Start Time Fault Reset

143 = Typical Specific Fault Reset

144 = Thermal Overload Warning Reset

145 = Thermistor Warning Reset

146 = Ground Fault Sum Warning Reset

147 = Unbalanced Load Warning Reset

148 = Phase Loss Warning Reset

149 = Emergency Stop Warning Reset

150 = Limit Switch Warning Reset

151 = Safety Circuit Warning Reset

152 = Main Circuit Warning Reset

153 = Control Circuit Warning Reset

154 = Switch Position Warning Reset

155 = Underload Current Warning Reset

156 = Overload Current Warning Reset

157 = External Supervision Warning Reset

158 = Long Start Time Warning Reset

159 = Typical Specific Warning Reset

160 = Contactor 1 Feedback Status Off

161 = Contactor 2 Feedback Status Off

162 = ESS DP Parameter Mode Off

163 = Switch Protected Status Off

164 = Start Attempt Status Off

165 = Drawer Ready Status Off

166 = General Warning Status Off

167 = General Fault Status Off

168 = Safety Circuit Status Off

169 = ESS DP Local Mode Status Off

170 = ESS DP Remote Mode Status Off

171 = Drawer Operation Mode Status Off

172 = Drawer Test Mode Status Off

173 = Limit Switch 1 Status Off

174 = Limit Switch 2 Status Off

175 = General Device Error Status Off

176 = Feedback Identification Status Off

177 = Class 1 Failure Off

178 = Modbus Failure Off

179 = Bypass Switched On Status Off

180 = Switching 1 Progess Status Off

181 = Switching 2 Progress Status Off

182 = Breaker Tripped Status Off

183 = Status Charged Status Off

184 = Torque Switching 1 Status Off

185 = Torque Switching 2 Status Off

186 = Start Phase Off

187 = Run Phase Off

188 = Thermistor Line Not Broken

189 = Thermistor Line Not Shorted

190 = Reserved Status 30 Off

191 = Reserved Status 31 Off

192 = Parameter No Error

193 = Watchdog No Error

194 = EEPROM No Error

195 = Start Attempt No Error

196 = Thermistor Test Not Fail

197 = Modbus ON 1 Off

198 = Modbus ON 2 Off

199 = Class 1 ON 1 Off

200 = Class 1 ON 2 Off

201 = Class 1 OFF Off

202 = Class 2 ON 1 Off

203 = Class 2 ON 2 Off

204 = Class 2 OFF Off

205 = Hardwire ON 1 Off

206 = Hardwire ON 2 Off

207 = Hardwire OFF Off

 

 

Unsigned Integer

Indicates the event type base on Index selected on holding

regsiter 101

90

16 bit

Event Tenths/Hundredths of Seconds

Unsigned Integer

Event of Input register 89 date and time

91

16 bit

Event Seconds

Unsigned Integer

92

16 bit

Event Minutes

Unsigned Integer

Event Time Stamp

93

16 bit

Event Hours

Unsigned Integer

Event Time Stamp

94

16 bit

Event Date

Unsigned Integer

Event Date

95

16 bit

Event Month

Unsigned Integer

Event Date

96

16 bit

Event Year

Unsigned Integer

Event Date

97

16 bit

“Analog RMS Value Log Data Ready

0 - Data Not Ready to be retrived

1 - Data Ready to be retrived”

 

 

Unsigned Integer

0 - Data not ready to be retrieved.

1 - Data ready to be retrieved.