4.41

 

 

 

 

 

Size

Telegram Name

Description

Default

Bytes

Unit

Scale

2 * 8-bit

B30008

Failure Telegram

2

 

5

BIT0 - Overload Failure

 

BIT1 - Phase Loss Failure

 

BIT2 - Ground Fault Failure

1 indicates Overload Failure (Trip)

 

1 indicates Phase Loss Failure (Trip)

 

1 indicates Ground Fault Failure (Trip)

 

 

 

 

6

BIT3 - Unbalanced Load Failure

 

BIT4 - Thermistor Failure

 

BIT5 - Emergency Stop Failure

 

BIT6 - Limit Switch Failure

 

 

BIT7 - Safety Circuit Failure

BIT0 - Main Circuit Failure

BIT1- Control Circuit Failure

IT2 - Switch Position (relay feedback) Failure

 

 

BIT3 - Under Load Current Failure

 

BIT4 - Overload / lock rotor etc Current Failure

 

BIT5 - External Supervision Failure

 

BIT6 - Long Start Failure

 

BIT7 - Typical Specific Failure

1 indicates Phase Unbalance Failure (Trip)

 

1 indicates Thermistor Failure (Trip)

 

1 indicates Emergency Stop Failure (Trip). Input must be mapped.

 

1 indicates Limit Switch failure - applicable to solenoid & actuator
typicals only.

 

1 indicates safety circuit failure. Input must be mapped.

 

1 indicates Main circuit failure. Input must be mapped.

 

1 indicates control circuit failure. Input must be mapped.

 

1 indicates contactor feedback position failure. Input must be
mapped.

 

1 indicates underload current failure (Trip).

 

1 indicates overload/lock motor failure.

 

1 indicates supervision circuit failure.

 

1 indicates long start.

 

Used on custom logic only.

 

 

 

 

2 * 8-bit

B30264

Warning Telegram

2

 

7

BIT0 - Overload Warning
BIT1 - Phase Loss Warning
BIT2 - Ground Fault Warning

BIT3 - Unbalanced Load Warning

BIT4 - Thermistor Warning

BIT5 - Emergency Stop Warning

BIT6 - Limit Switch Warning

BIT7 - Safety Circuit Warning

1 indicates Overload warning

1 indicates Phase Loss warning

1 indicates Ground Fault warning

1 indicates Phase Unbalance warning

1 indicates Thermistor warning

 

 

 

 

8

BIT0 - Main Circuit Warning

BIT1 - Control Circuit Warning

BIT2 - Contactor Feedback Warning
BIT3 - Under Load Current Warning
BIT4 - Over Load Current Warning
BIT5 - External Supervision Warning
BIT6 - Long Start Warning

BIT7 - Typical Specific Warning

1 indicates Overload warning

1 indicates Phase Loss warning

1 indicates Ground Fault warning

1 indicates Phase Unbalance warning

1 indicates Thermistor warning

 

 

 

 