GE Industrial Solutions EntelliPro ES User Manual

Page 158

Advertising
background image

EP OS MOTOR MANAGEMENT SY STEM – INSTRUCTION MANUAL

4.21

CHAPTER 4: COMMUNICATION

 

 

 

 

 

Holding

Register

Modbus

Size

Variable

Description

Min

Max

Step

Units

Scale

Format

Default

76

16 bit

Time Sync Year

 

 

 

 

Values to write to Real Time Clock (RTC)
Note:Function code 05 command 181 will be
required after setting registers 76 thru 83.

 

 

 

 

Year

Unsigned

Integer

 

77

16 bit

Time Sync Month

 

 

 

 

Month

Unsigned

Integer

 

78

16 bit

Time Sync Date

 

 

 

 

Date

Unsigned

Integer

 

79

16 bit

Time Sync Day

 

 

 

 

Da

y

Unsigned

Integer

 

80

16 bit

Time Sync Hour

 

 

 

 

Hour

Unsigned

Integer

 

81

16 bit

Time Sync Minute

 

 

 

 

Minute

Unsigned

Integer

 

82

16 bit

Time Sync Second

 

 

 

 

Sec

ond

Unsigned

Integer

 

83

16 bit

Time Sync Tenths/Hundredths of Seconds

 

 

 

 

1/10

0th

Seco

nd

Unsigned

Integer

 

90

16 bit

ModbusCommunicationSetting;

 

0 - ModbusComSetting_3008N2

 

1 - ModbusComSetting_6008N2

2 - ModbusComSetting_12008N2

3 - ModbusComSetting_24008N2

4 - ModbusComSetting_48008N2

5 - ModbusComSetting_96008N2

6 - ModbusComSetting_192008N2

7 - ModbusComSetting_3008O1

8 - ModbusComSetting_6008O1

9 - ModbusComSetting_12008O1

10 - ModbusComSetting_24008O1

11 - ModbusComSetting_48008O1

12 - ModbusComSetting_96008O1

13 - ModbusComSetting_192008O1

14 - ModbusComSetting_3008E1

15 - ModbusComSetting_6008E1

16 - ModbusComSetting_12008E1

17 - ModbusComSetting_24008E1

18 - ModbusComSetting_48008E1

19 - ModbusComSetting_96008E1

20 - ModbusComSetting_192008E1

21 - ModbusComSetting_3008N1

22 - ModbusComSetting_6008N1

23 - ModbusComSetting_12008N1

24 - ModbusComSetting_24008N1

25 - ModbusComSetting_48008N1

26 - ModbusComSetting_96008N1

27 - ModbusComSetting_192008N1

Set Baud Rate, Parity, Data Bits, Stop Bits

 

 

Example:

3008N2

300 = Baud Rate

8 = Data Bits

N = No Parity (E = Even Parity, O = Odd Parity)

2 = Stop Bits

0

27

1

 

 

Unsigned

Integer

27

91

16 bit

Frequency

0 - 50Hz

1 - 60Hz

0

1

1

 

 

Unsign

ed

120 = 1.2A

e

x100

120 = 1.2A

x100

Integer

 

92

(L)

 

32

bit

register 92 = 14. Combine both HEX numbers = 143E8. Convert this number to decimal = 82920. This corresponds to 829.2A base on the x100 scale factor.

 

Current Sensor Rating Low Speed (Ict_

lowspeed)

Sensor setting

10

65000

1

Amps

 

Unsigned

Integer

120

93

(H)

 

 

 

 

 

 

94

(L)

 

32 bit

 

Motor Rating Low Speed

Motor Load setting

1/6*Ict_

lowspeed

Ict_

lowspeed

 

1

 

Amps

 

Unsigned

Integ

er

x100

20 = 0.2A

20

95

(H)

96

(L)

 

32 bit

Current Sensor Rating High Speed (Ict_

highspeed)

Sensor setti

n

127(

Interpretation of 32-bit value.

Example register 91 (L = low word) = 1000 register 92 (H = high word) = 20. Convert both registers to HEX: regsiter 91 = 3E8, .

g

10

65000

 

1

 

Amps

 

Unsigned

Integer

120

97

(H)

98

(L)

 

32 bit

 

Motor Rating High Speed

Motor Load setting

1/6*Ict_

highspeed

Ict_

highspeed

 

1

 

Amps

 

Unsign

ed

x100

20 = 0.2A

Integer

20

99

(H)

100

16 bit

Motor Feedback Enabled

Allows motor to start without any feedback

0 - No feedback required

1 - Feedback required

Read Only register

0

1

1

 

 

Unsigned

Integer

1

101

16 Bit

Event Read Index

input register112 - Modbus FC 04

Modbus FC 04. Last event index is shown on

Event to be displayed on input register 89 - 96

0

249

1

 

 

Unsigned

Integer

0

102

16 bit

Modbus Software / Front Switch Selection

0 - Use Modbus software address set on

holding register 103

1 - Use Modbus address from the front

switches

0

1

1

 

 

Unsig

ned

Integer

1

103

16 bit

ModbusSlaveAddress

Modbus Software Slave address

1

247

1

 

 

Unsigned

Integer

1

104

16 bit

Profibus_ID_Number

EntelliPro ES Retrofit = 0x0574

EntelliPro ES = 0x0500

 

 

 

 

 

Unsigned

Integer

 