EP OS MOTOR MANAGEMENT SY STEM – INSTRUCTION MANUAL

4.15

CHAPTER 4: COMMUNICATION

 

 

 

 

4.1.10.6 Function Code

14H

 

Modbus Implementation: Read File Record

 

EntelliPro Implementation: Read Full Event and Analog Data

 

This command allows the master to read a file containing the full 255 events and analog RMS data. All Request

Data Lengths are provided in terms of number of bytes and all Record Lengths are provided in terms of registers.

 

 

Master Transmission

Bytes

Value

 

Slave Address

1

1 - 245

Function Code

1

0x14

Byte Count

1

0x07 to 0xF5

Reference Type

2

06

File Number

2

0x0001 (Read all 255 Events)

0x0002 (Read Current RMS)

Record Number

2

0x 0000 to 0x03E8

Register Length

2

0x0000 to 0 x 007B

 

 

Table 4-8: Function Code

14H

 

 

4.1.10.7 Function Code 1

5H

Modbus Implementation: Write File Record EntelliPro Implementation: Write

“Custom” logic

 

This command allows the master to write a file containing the custom logic to the EntelliPro ES. This function code is
used to perform a file record write. All Request Data Lengths are provided in terms of number of bytes and all Record
Lengths are provided in terms of the number of 16-bit words.

 

 

Master Transmission

Bytes

Value

 

Slave Address

1

1 - 245

Function Code

1

0x15

Reference Type

1

06

File Number

2

0x03FF

Record Number

2

 

Record Number

2

 

Register Length

2 x N

 

 

Table 4.9 Function Code 1

5H