CHAPTER 3: MOTOR PR OTECTION

3.16

EP OS MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL

 

 


When the auto-reset parameter is set to 1, the Auto-Reset is allowed after an overload trip occurred.

 

NOTE:

auto reset will NOT be allowed for 1 hour after the last trip.

 

 

When the auto-reset parameter is set to 2, 2 auto-Resets are allowed after an overload trip occurred.

 

NOTE:

auto reset will NOT be allowed for 1 hour after the second trip.

 

 

When the auto-reset parameter is set to 3, 3 auto-resets are allowed after an overload trip occurred.

 

NOTE:

auto reset will NOT be allowed for 1 hour after the third trip.

 

 

The auto-reset can be set to higher values if ATEX is disabled. For settings above 4, auto-

reset is always allowed.

 

 

NOTE:

If the EntelliPro ES is configured as an ATEX device, the n-times reset cannot be set to “always” auto- reset .

 
 

 