CHAPTER 2: INSTALL ATION/CONFIGURATION

2.68

EP OS MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL

 

 

When limit switch 2 is reached (input 96 on EntelliPro ES3 and input 19 on EntelliPro ES5) a “switch position” warning or
a fault will be generated.

CAUTION:

The phase system in WinESG parameterization\device settings panel shown in the illustration below or

Modbus function code 6 register 5 must be set to 1 phase if the system is a 1 phase system for proper overload
protection.

If the default configuration and the solenoid typical are selected in the WinESG parameterization/information panel
shown in the illustration below or by setting Modbus function code 6 register 62 bit0 to 1 and bits 8,9,10 and 11 to
0x9,the inputs and outputs are mapped as below:

For EntelliPro ES3 types:

Input 99 is mapped to contactor 1 feedback

- active high

Input 98 is mapped to main circuit

- active low

Input 97 is mapped to limit switch 1 reached

- active low

Input 96 is mapped to limit switch 2 reached

- active low

Input 95 is mapped to emergency stop

- active low

Input 94 is mapped to external supervision

- active high

Input 93 is mapped to safety circuit

- active low

Output 41 is mapped to contactor 1

Output 43 is mapped to command ON1 (start)

Output 45 is mapped to failure