EP OS MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL

CHAPTER 4: COMMUNICATION

 

 

 

 

4.1.11 Error Responses

 

When a EntelliPro ES detects an error other than a CRC error, a response will be sent to the master. The MSBit of the
FUNCTION CODE byte will be set to 1 (i.e. the function code sent from the slave will be equal to the function code sent
from the master plus 128). The following byte will be an exception code indicating the type of error that occurred.
Transmissions received from the master with CRC errors will be ignored by the EntelliPro ES.

 

The slave response to an error (other than CRC error) will be:

 

Slave Address:

1 byte

 

Function Code:

1 byte (with MSbit set to 1)

Exception Code:

1 byte

Crc: 2

bytes

 

 

The EntelliPro ES implements the following exception response codes:

 

01 - Illegal Function

The function code transmitted is not one of the functions supported by the EntelliPro ES.

 

02 - Illegal Data Address

The address referenced in the data field transmitted by the master is not an allowable

address for the EntelliPro ES.

 

03 - Illegal Data Value

The value referenced in the data field transmitted by the master is not within range for the

selected data address.