EP OS MOTOR MANAGEMENT SY STEM – INSTRUCTION MANUAL

4.17

CHAPTER 4: COMMUNICATION

 

 

 

 

4.1.12 Modbus Register Map

 

Function Code 03 - Read Holding Registers Function Code 06
- Write Holding Registers Function Code 16 Write Multiple

Holding Registers

 

 

Holding

Register

Modbus

Size

 

Variable

Description

Min

Max

 

Step

 

Units

 

Scale

Format

Default

 

 

 
 

 

 
 

 

 

 

 

 

 

5

 

16 bit

 

Basic Parameter Setting

 

0

255

 

1

 

n/a

 

n/a

Unsigned

Integer

6

 

Bit0 -

0 = (0-20mA) Analog Output selected

1 = (4 - 20mA) ] - Analog Output selected

Selection of Analog Output type

 

 

 

 

 

 

 

 

Bit1 - [ 0 - OFF, 1 - ON] -- Overload Memory

1 means use store data in EEProm:

- Trip condition -(trip or not for LT and

Thermistor) - if trip condition is set in
EEProm, motor cannot be started until
the motor is cooled and warning or fault

is reset.

Reset cooling:

- FC 06 register 13 set to zero

- FC 05 register 144

0 means do not use EEPROM data - no faults or

warnings are saved upon power down

 

 

 

 

 

 

 

 

Bit2 - [ 0 - Immediate , 1 - Delayed] - Max

Current

0 = perform max current monitoring

immediately

1= delayed the max current monitoring by 2

minutes (after motor start)

 

 

 

 

 

 

 

 

Bit3 - Free

 

 

 

 

Bit4 - Debug Mode

0 = OFF

1 - ON -

Debug mode = ON

- Additional Profibus DP telegram will be

available:

V4 retrofit = telegram B2721

V5 = telegram B40005

 

 

 

 

 

 

 

 

Bit5, Bit6 - Phase Selection

00 => 3-Phase

01 => 2-Phase (Bit5 = 1, Bit6 = 0)

10 => 1-Phase (Bit5 = 0, Bit6 = 1)

Number of phase selection

 

 

 

 

 

 

 

 

Bit7 - TwoSpeedMotor

Type of motor selection

0 - disable

1 - enable (use for pole changer and

Dahlander typicals)

 

 

 

 

 

 

 

6

16 bit

Bus Failure Behavior

bit0 - bit 3

1 - Ignore - Profibus Class1 Failure

2 - Delayed OFF

3 - Delayed ON1

4 - Delayed ON2

bit 4 - bit 7

1 - Ignore - Modbus Failure

2 - Delayed OFF

3- Delayed ON1

4- Delayed ON2

Behavior of the EntelliPro ES upon

Communication Bus Failure

 

Delay Motor stop

Delay Motor forward ON
Delay Motor reverse ON

 

 

Delay Motor stop

Delay Motor forward ON
Delay Motor reverse ON

0

255

1

n/a

n/a

Unsigned

Integer

1

12

16 bit

Overload Delay

1 - Class5

2 - Class10

3 - Class15

4 - Class20

5 - Class25

6 - Class30

7 - Class35

8 - Class40

Overload Trip Class selection

1

8

1

n/a

n/a

Unsigned

Integer

1

13

16 bit

Overload Cooling Constant

Cooling algorithm selection

0 = No thermal memory

0

15

1

n/a

n/a

Unsigned

Integer

15

14

16 bit

Ground Fault Pick-Up

 

2

8

1

%

GF PU

Setting

x 10

2 = 20%

Unsigned

Integer

2