GE Industrial Solutions EntelliPro ES User Manual

Page 164

Advertising
background image

EP OS MOTOR MANAGEMENT SY STEM – INSTRUCTION MANUAL

4.27

CHAPTER 4: COMMUNICATION

 

 

 

 

 

Holding

Register

Modbus

Size

Variable

Description

Min

Max

Step

Units

Scale

Format

Default

130

16 bit

Configuration Bits

bit 0 - Class1BusFailureDetection

bit 1 - ModbusBusFailureDetection

bit 2 - ActivateThermistorLineBreakAnd

ShortedSupervision

bit 3 - ActivateDrawerPositionSupervision

bit 4 -

 

bit 5 - Remote Source Control OFF

0 - disabled

1- enabled

0 - disabled

1- enabled

0 - disabled

1- enabled

0 - disabled

1- enabled

If set to 1; Switch is set to LOCAL but and OFF

command from Remote source is accepted

0

127

 

 

 

Unsigned

Integer

5

132

16 bit

Firmware Version

Read only

Definition:

Firmware Version “000.000” => “HigherByte.
LowerByte”

 

 

 

 

 

Unsigned

Integer

0x01

134

16 bit

Free Logic Version[0 & 1]

Read only

 

 

0

135

16 bit

Free Logic Version[2 & 3]

Read only

 

 

0

136

16 bit

Free Logic Version[4 & 5]

Read only

 

 

0

162

16 bit

Serial Number[0 & 1]

Serial Number

 

 

 

 

 

Unsigned

Integer

 

163

16 bit

Serial Number[2 & 3]

 

 

164

16 bit

Serial Number[4 & 5]

 

 

165

16 bit

Serial Number[6 & 7]

 

 

166

16 bit

Serial Number[8 & 9]

 

 

167

16 bit

Serial Number[10 & 11]

 

 

169

170

32 bit

Operating Hour

Hour of operation

0

4294967296

1

Hour

 

Unsigned

Integer

 

171

172

32 bit

Motor Start Counter

Number of Motor Start

0

4294967296

1

 

 

Unsigned

Integer

 

173

174

32 bit

Switch Counter[0]

Number of operation of motor contactor 41

0

4294967296

1

 

 

Unsigned

Integer

 

175

176

32 bit

Switch Counter[1]

Number of operation of motor contactor 42

0

4294967296

1

 

 

Unsigned

Integer

 

177

178

32 bit

Switch Counter[2]

Number of operation of motor contactor 43

0

4294967296

1

 

 

Unsigned

Integer

 

179

180

32 bit

Switch Counter[3]

Number of operation oof motor contactor 45.

Mainly use on start-delta reverse typical

0

4294967296

1

 

 

Unsigned

Integer

 

181

16 bit

Thermal overloaf trip Counter

Thermal Overload Trip Counter

0

65536

1

 

 

Unsigned

Integer

 

182

16 bit

Thermistor Trip Counter

Thermistor Trip Counter

0

65536

1

 

 

Unsigned

Integer

 

183

16 bit

Ground Fault Sum trip Counter

Ground Fault Sum trip Counter

0

65536

1

 

 

Unsigned

Integer

 

184

185

32 bit

Non-Operation Hour

Hour of non-operation - motor stopped

0

65536

0

Hour

 

Unsigned

Integer

 

194

16 bit

Digital Output - Signal Relay 23

See Digital Output 0 for configuration and

setting (Holding register 126)

1

71

1

 

 

Unsigned

Integer

5

195

16 bit

DigitalOutput - Signal Relay 24

See Digital Output 0 for configuration and

setting (Holding register 126)

1

71

1

 

 

Unsigned

Integer

5

196

16 bit

DigitalOutput - Signal Relay 25

See Digital Output 0 for configuration and

setting (Holding register 126)

1

71

1

 

 

Unsigned

Integer

5

197

16 bit

DigitalOutput - Signal Relay 26

See Digital Output 0 for configuration and

setting (Holding register 126)

1

71

1

 

 

Unsigned

Integer

5

237

16 bit

ESS-type name[0 & 1]

Read Only

Catalog Number

 

 

 

 

 

Unsigned

Integer

 

238

16 bit

EntelliPro ES-type name[2 & 3]

 

 

239

16 bit

E

ntelliPro ES-type name[4 & 5]

 

 

240

16 bit

E

ntelliPro ES-type name[6 & 7]

 

 

241

16 bit

E

ntelliPro ES-type name[8 & 9]

 

 

242

16 bit

E

ntelliPro ES-type name[10 & 11]

 

 

243

16 bit

E

ntelliPro ES-type name[12 & 13]

 

 

244

16 bit

E

ntelliPro ES-type name[14 & 15]

 

 

245

16 bit

E

ntelliPro ES-type name[16 & 17]

 

 

246

16 bit

E

ntelliPro ES-type name[18 & 19]

 

 

247

16 bit

E

ntelliPro ES-type name[20 & 21]

 

 