EP OS MOTOR MANAGEMENT SY STEM – INSTRUCTION MANUAL

CHAPTER 5: WinESG

5.1

5

 

 

Figure 5-8: WinESG parameterization device setting panel

Illustration A shows the current setting.

CT rated current (Ict):

current transformer (CT) primary current. It is the upper value of

the CT

range divided by the feed-thru factor. The feed-thru factor is how often
the primary conductor is fed through the CT. For single conductor CT
the value on the label used. The maximum allowed C current is 6400A.

Table below shows the CT rated current in Ampere for different CTs and feed-thru factors.

Motor rated current (Ir):

settable in the range of 1 to 1/6 x Ict. This value is used for overload,
ground fault, and current thresholds protections

Two Speed motor:

only applicable for two-speed motors (Dahlander, Pole changer typicals).
When applicable a second CT and motor current can be set for the
additional speed. All other parameters are applicable to both speeds.

Phase:

select the system type: 3-Phase, 2-Phase, and 1-Phase.

1

2

3

4

8

Entellipro CT8

8

4

2.67

2

1

Entellipro CT32

32

16

10.67

8

4

Entellipro CT64

64

32

21.33

16

8

Entellipro CT630

630

315

210

157.50

78.75

Feed-thru Factors

A

B

C

D

F

G