EP OS MOTOR MANAGEMENT SY STEM – INSTRUCTION MANUAL

4.31

CHAPTER 4: COMMUNICATION

 

 

 

 

 

Input

Register

Address

Data

Size

 

Parameter Name

Units

Scale

Format

Note

100

101

32 bit

EntelliPro

ES Status

bit0 - Contactor1FeedbackStatus

bit1 - Contactor2FeedbackStatus

bit2 – ParameterModeStatus

 

bit3 - SwitchProtectedStatus /
BlockLocalSwitchON

 

bit4 – StartAttempt

 

 

bit5 – DrawerReadyStatus

bit6 – GeneralWarningStatus

bit7 – GeneralFaultStatus

 

bit8 - Safety circuitStatus

bit9 - ESS_DPLocalModeStatus

bit10 - ESS_DPRemoteModeStatus

 

bit11 - DrawerOperationMode Status

bit12 - DrawerTestModeStatus

 

bit13 - LimitSwitch1Status

 

 

bit14 - LimitSwitch2Status

 

bit15 – GeneralDeviceErrorStatus

bit16 – Feedback_IdentificationStatus

bit17 - Class1Failure

bit18 - ModbusFailure

bit19 - ByPassSwitchedON

 

 

bit20 - Switching1Progress

bit21 - Switching2Progress

bit22 - BreakerTripped2

bit23 -StatusCharged

bit24 - TorqueSwitching1Progress

bit25 - TorqueSwitching2Progress

bit26 -StartPhase

 

bit27 -RunPhase

 

bit28 - ThermistorLineBroken

 

 

bit29 -Thermistor Line Shorted

 

 

Unsigned Integer

Status Definition

When Relay 41 is turned ON , on receiving the feedback signal
from of the the mapped input, the status will be set to 1

 

When Relay 43 is turned ON , on receiving the feedback signal

from of the the mapped input, the status will be set to 1

 

When an OFF command is received by the Remote source,
and the switch control is set to local, and the block local
switch ON is actiavted, the status will be set to 1

 

When the Start attempts exceeds the parmeterized

counter,the status will be set

 

When there is no fault or device error, the local-remote-off
switch position is set, drawer mode is selected and no OFF
command is issued, status will be set to 1

 

When any warning exist, the status will be set to 1

 

When any fault exist, the status will be set to 1

 

When there is safety circuit digital input, this bit would be
set to 1

 

When the local-remote-off switch is set to local, the status will

be set to 1 source

 

When the local-remote-off switch is set to remote, the status
will be set to 1 source

 

When drawer is in operation mode, the status will be set to 1

 

When drawer is in test mode, the status will be set to 1

 

When limit switch1 digital input is present, the status will be
set to 1

 

When limit switch2 digital input is present, the status will be
set to 1

 

When any of device error exist, the status will be set to 1

 

When command is received to identify the EntelliPro ES, the
status will be set to 1

 

When there is a Profibus Class1 failure, the status will be

set to 1

 

When there is a Modbus failure, the status will be set to 1

 

Typical Specific-- Need to have corresponding digital input

 

When relay 41 is ON and no feedback is yet received, the

status will be set to 1

 

When relay 43 is ON and no feedback is yet received, the
status will be set to 1

 

Typical Specific-- Need to have corresponding digital input

Typical Specific-- Need to have corresponding digital input

Typical Specific-- Need to have corresponding digital input

Typical Specific-- Need to have corresponding digital input

 

When the motor is in the start phase, the status will be set
to 1

 

When the motor is in the run phase, the status will be set to 1

 

When there is thermistor open failure, the status will be set
to 1

 

When there is thermistor short failure, the status will be set
to 1