CHAPTER 2: INSTALL ATION/CONFIGURATION

2.12

EP OS MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL

 

 

 
 
 

 

Register

Description

Bit Definition

115

Bit0 thru Bit2 defines the Remote source

 

Bit0 – Bit 2

 

 

 

Bit4 thru Bit6 defines the source that controls the local/

remote/ off switch

 

Bit 0- bit 2

 

 

0 - None

1 - Profibus Class 1

2- Modbus

3-Hardwire

 

 

 

0- None

1- Profibus Class 1

2-Modbus

3-Hardwaire

4-Fixed Local

5-Fixed Remote

 

Table 2-5 Remote source and switch control selection via Modbus

 


To start contactor1, Modbus command function code 5 register 11 set to ON selects the remote source
(Modbus), as a means to control the start/stop/reset operations. This command may be issued only once
upon power up.

 

Once the remote selection is made, a start command can be issued using Modbus function code 5 register
1.

 

To start contactor2, Modbus command function code 5 register 11 set to ON selects the remote source
(Modbus), as a means to control the start/stop/reset operations.. Once the remote selection is made a start
command can be issued using Modbus function code 5 register 2.

 

To start the contactors, Modbus command function code 5 register 10 set to ON selects the local sources
(hardwire, Modbus RTU and WinESG), as a means to control the start/stop/reset operations. This command
may be issued only once upon power up.

 

Once the local selection is made, a start command can be issued from any local sources.