4.24

EP OS MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL

CHAPTER 4: COMMUNICATION

 

 

 

 

 

Holding

Register

Modbus

Size

Variable

Description

Min

Max

Step

Units

Scale

Format

Default

118

16 bit

Digital Input[9

8 & 99]

 

Setting example:

Digital 0 is mapped to Reset alarm Input

Signal = 14

Digital 1 is mapped to Reset alarm Input

Signal = 15

1514 decimal = 0x0F0D

Covert 0x0F0D to decimal (3853)
Place 3853 into this register

Active High Configuration

01 = Contactor 1 ON Command

02 = Contactor 2 ON Command

03 = Contactor 1/2 OFF Command

04 = Contactor 1 Feedback / MCCB ON

Feedback

05 = Contactor 2 Feedback / MCCB OFF

Feedback

06 = Start Contactor Feedback Signal

Breaker Charged Status Signal
Bypass Feedback

Limit Switch 2

Limit Switch Close

07 = Feedback 4

Delta Contactor Feedback Signal
Soft Starter Up to Speed Feedback
Torque Switch1

Torque Open/ Breaker tripped 2

08 = External Fault Signal 1

External Supervision Feedback

09 = Breaker ready for switch ON

Torque Close

Torque Switch 2

10 = Drawer Test Position Signal

11 = Drawer Operation Position Signal

12 = Remote Input Signal

13 = Local Input Signal

14 = Reset Alarms Input Signal

15 = Main Circuit Feedback

16 = Control Circuit Feedback

17 = Emergency Stop Signal

18 = Safety Circuitry Signal

19 = Limit Switch 1

Limit Switch Open

Soft Starter External Fault

Breaker Tripped 1

20 = External Fault Signal 2

Active Low Configuration

21 = Contactor 1 ON Command

22 = Contactor 2 ON Command

23 = Contactor 1/2 OFF Command

24 = Contactor 1 Feedback / MCCB ON

Feedback

25 = Contactor 2 Feedback / MCCB OFF

Feedback

26 = Start Contactor Feedback Signal

Breaker Charged Status Signal
Bypass Feedback

Limit Switch 2

Limit Switch Close

27 = Feedback 4

Delta Contactor Feedback Signal

Soft Starter Up to Speed Feedback
Torque Switch1

Torque Open

Breaker Tripped 2

28 = External Fault Signal 1

External Supervision Feedback

29 = Breaker Ready for Switch ON

Torque Close

Torque Switch 2

30 = Drawer Test Position Signal

31 = Drawer Operation Position Signal

32 = Remote Input Signal

33 = Local Input Signal

34 = Reset Alarms Input Signal

35 = Main Circuit Feedback

36 = Control Circuit Feedback

37 = Emergency Stop Signal

38 = Safety Circuitry Signal

39 = Limit Switch 1

Limit Switch Open

Soft Starter External Fault

Breaker Tripped 1

40 = External Fault Signal 2

1

65536

1

 

 

Unsigned

Integer

10244