EP OS MOTOR MANAGEMENT SY STEM – INSTRUCTION MANUAL

4.19

CHAPTER 4: COMMUNICATION

 

 

 

 

 

Holding

Register

Modbus

Size

Variable

Description

Min

Max

Step

Units

Scale

Format

Default

56

1

16 bit

Current Unbalance/Loss Delay

0-Disable

0

15

1

sec

 

Unsigned

Integer

1

57

16 bit

Analog RMS value time interval

Time interval between analog value log

samples

Example: If set to 60 - every 60 secs a

sample is recorded

1

60

1

sec

 

Unsigned

Integer

1

58

16 bit

Analog RMS Value Trigger

Bit0, Bit1, Bit2 - Event to stop storage

0 - Disable

1 - Trip

2 - Warning

3 - Switch ON

4 - Switch OFF

5 - Manual

Bit 3 -

0 - 3/4 pre and 1/4 post trigger data

1 - 1/4 pre and 3/4 post trigger data

Bit 4 - Reserved
Bit 5 - Reserved
Bit 6 - Reserved

Bit 7 - Reserved

Trigger mechanism

 

 
 

 

 
 

 

Number of pre and post trigger samples
recorded.

0

15

1

 

 

Unsigned

Integer

0

59

16 bit

Modbus Timeout Timer

Time allowed between Modbus messages until

Modbus error is generated

1

120

1

sec

 

Unsigned

Integer

 

62

16 bit

Special Functions

Bit0 = Default Configuration

 

 

Bit1 = Disable alarm underload current

Bit2 - Disable alarm overload current

 

Bit3-4 Parameterization configuration

 

 

 
 

 

 
 

 

 

Bit 5 - Ignore Phase loss during start phase

 

 

Bit 6 - Ignore earth fault during start phase

 

 

Bit 7 - Ignore Unbalance load during start
phase

 

Bit 8 to 11- Typical selection

 

 

 
 

 

 
 

 

 

Bit 12 to 15 - Control mode variant selection

If set to 1 - typical and control mode default

configuration will be used.

 
 

 

 

0 0 - parameterization allowed via Profibus DP

only when motor is in stop condition

0 1 - parameterization allowed via Profibus DP

while motor is at any state.

1 0 - parameterization allowed via Profibus

DP when draw out position is not in test or
operation mode

11 - parameterization allowed via Profibus

DP when the operation mode is not Remote

or Local. Note: the Modbus operation mode
selection is done using function code 05 -
commands 10 or 11

 

1 - Ignored phase loss during start-up

0 - Do not ignore

 

1 - Ignored earth fault during start-up

0 - Do not ignore

 

1 - Ignored current unbalance during start-up

0 - Do not ignore

 

0xX0XX = DOL

0xX1XX = DOL Reverse

0xX2XX = Start Delta

0xX3XX = Start Delta Reverse

0xX4XX = Soft Starter

0xX5XX = Soft Starter Reverse

0xX6XX = Dahlander

0xX7XX = Pole Change Starter

0xX8XX = Breaker Control

0xX9XX = Solenoid Valve

0xXAXX = Actuator

0xXBXX = Custom Logic

 

1 - 6 - Refer to Chapter 2, Section 2.4.2

0

255

1

 

 

Unsigned

Integer

 

 

 
 

 

 

 
 

 

1: If ATEX is selected, the current unbalance/loss delay is automatically set to trip immediately.