CHAPTER 2: INSTALL ATION/CONFIGURATION

2.20

EP OS MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL

 

 

 

 

2.3 Motor Starter Configuration

 

There are eleven pre-programmed starter types (typicals), which can be selected via Modbus RTU or Profibus
communication..

 

The following are the starter types:

Full-voltage non-reversing

 

Full-voltage reversing

 

Star-delta open transition

 

Star-delta reverse open transition

 

Soft starter

 

Reverse soft starter

Breaker Control (see note below)

Dahlander

Pole changer

 

Solenoid valve

 

Actuator with limit or torque switch

 

 

In additional customers can order customized motor starter arrangement by providing GE with desired logic control for
inputs, outputs and timers.

 

 

NO

TE:

NOTE:

Customer can change pre-defined configurations of any motor starter if the default configuration is

not

to simulate the application.

Breaker Control selection is NOT available on EntelliPro ES Revision 1.002. Custom logic can be created to

selected.

 

 

To select the motor starter type via Modbus, holding register 62 bit 8 to 11 should be used. Refer to Chapter 4 for
additional Modbus information. WinESG

parameterization/information panel shown in the illustration below can be

used to configured the motor starter type.

 

 


WARNING:

If

“allow direction switchover” is enabled, make sure the “motor ON direction switchover time” 

timer exceeds the contactor or breaker clearing time to avoid short circuit.