K = cooling factor units = seconds – GE Industrial Solutions EntelliPro ES User Manual

Page 119

Advertising
background image

CHAPTER 3: MOTOR PR OTECTION

EP OS MOTOR MANAGEMENT SY STEM – INSTRUCTION MANUAL

3.7

 

 

 

 

M otor

Heating

Class 5

K = 1

Class 5

K = 2

Class 5

K = 3

Class 5

K = 4

Class 5

K = 5

Class 5

K = 6

Class 5

K = 7

Class 5

K = 8

Class 5

K = 9

Class 5

K = 10

Class 5

K = 11

Class 5

K = 12

Class 5

K = 13

Class 5

K = 14

Class 5

K = 15

100

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

90

16.2

32.4

48.6

64.8

81

97.2

113.4

129.6

145.8

162

178.2

178.2

178.2

226.8

243

80

34.2

68.4

102.6

136.8

171

205.2

239.4

273.6

307.8

342

376.2

376.2

376.2

478.8

513

70

54.75

109.5

164.25

219

273.75

328.5

383.25

438

492.75

547.5

602.25

602.25

602.25

766.5

821.25

60

78.45

156.9

235.35

313.8

392.25

470.7

549.15

627.6

706.05

784.5

862.95

862.95

862.95

1098.3

1176.75

50

106.35

212.7

319.05

425.4

531.75

638.1

744.45

850.8

957.15

1063.5

1169.85

1169.85

1169.85

1488.9

1595.25

40

140.7

281.4

422.1

562.8

703.5

844.2

984.9

1125.6

1266.3

1407

1547.7

1547.7

1547.7

1969.8

2110.5

30

184.8

369.6

554.4

739.2

924

1108.8

1293.6

1478.4

1663.2

1848

2032.8

2032.8

2032.8

2587.2

2772

20

247.05

494.1

741.15

988.2

1235.25

1482.3

1729.35

1976.4

2223.45

2470.5

2717.55

2717.55

2717.55

3458.7

3705.75

10

353.4

706.8

1060.2

1413.6

1767

2120.4

2473.8

2827.2

3180.6

3534

3887.4

3887.4

3887.4

4947.6

5301

 

Figure 3-3: Thermal cooling model when trip curve is set to IEC class5

 

K = Cooling Factor

Units = seconds