3 profibus interface – GE Industrial Solutions EntelliPro ES User Manual

Page 172

Advertising
background image

CHAPTER 4: COMMUNICATION

EP OS MOTOR MANAGEMENT SY STEM – INSTRUCTION MANUAL

4.35

 

 

Communication

Solid amber

Cyclic communication ok

 

Random flashing amber

Acyclic communication / Modbus

communication

 

Flashing one second ON

one second OFF

No Profibus or Modbus communicatio

or communication error

 

 

4.2.3 Profibus Interface

 

The EntelliPro ES supports DPV0 and DPV1 protocols, which

is comprised of Cyclic and Acyclic data transfer.

The external connections through the Profibus interface (female D-sub connector) are as follows:

 

 

D-Sub Connector Pin

Connection (external device)

 

 

V–

Pin 5

 

 

L

Pin 8, line A (negative TX/RX)

 

H

Pin 3, line B (positive TX/RX)

 

V+

Pin 6

 

 

 

Table 4.10 Profibus interface external connections

 

 

The Communication LED indicates the status of Profibus interface:

 

LED Color

Description

 

 

 
 

 

n

 

 

 

Table 4.11 Profibus LED indications

 

 

When used for Profibus, the Fieldbus port has the following characteristics:

Baud rate: 9600, 19200, 93750, 187500, 500000, 1.5M, 3M, 6M and 12M bps (with autodetect)

 

Address: 1 to 125 – settable through the front switches. Switches setting above 125, will default

to

126.

 

Vendor ID: 0x500E

 

Data table size: Max_Data_Len = 162, Input_Data_Len = 144 bytes, Output_Data_Len = 18 bytes

 

The Profibus DP Master must read the GSD (Device Master Data) file of the EntelliPro ES for the purposes of
configuration and parameterization. The GSD file for the EntelliPro ES is named GE500E.GSD and it is
available on the WinESG CD

.

 

 