CHAPTER 2: INSTALL ATION/CONFIGURATION

EP OS MOTOR MANAGEMENT SY STEM – INSTRUCTION MANUAL

2.1

 

 

 

 

GE Industrial Solutions

 

 

 

 

 

EPOS Motor Management System

 

Chapter 2: Installation / Configuration

 

 
 

 

2.1 Installation and initial operating

 

The EntelliPro ES is an intelligent motor control relay that is mainly installed in low voltage systems for industrial usage.
To ensure safe operation, several measures must be taken.

 

CAUTION:

Only use genuine draw out units produced by the factory. Observe proper cable laying in the cable terminal

compartment and outside the switch cabinet.

 

CAUTION:

Only qualified personnel are allowed to install, commission, maintain or modify this device in accordance

with relevant requirements.

 

 

The following tables show the recommended cable type and spacing.

 

Cable type

Category

power cable (400VAC....) A

control cable

B

function cable (TMA, ...)

C

bus cable

D

 

Table 2-1: Recommended EntelliPro ES Cable listing

 

 
 

 

Table 2-2: Recommended cable spacing

 

NOTES:

 

Do not use multi-stranded cable with combinations from categories A to D.

 

The PE-connection of the EntelliPro ES must be connected.

 

The maximum length of the connection cable to the current transformer is 20 cm.

 

Before initial commissioning of the installation the communication bus wiring and the signal quality must be

tested with a Profibus/Modbus test and diagnostic device.

 

All wires connected to the EntelliPro ES- modules must be checked prior to operation.

 

 

 
 