CHAPTER 1: INTR ODUCTION

EP OS MOTOR MANAGEMENT SY STEM – INSTRUCTION MANUAL

1.9

 

 

 

 

1.2 Specifications

 


NOTE:

Specifications are subject to change without notice.

 

 

1.2.1 Protection Specifications

 



Overload Fault (Thermal Model)

IEC Class curves ....................................................................5, 10, 15, 20, 25, 30, 35, 40 (IEC 60947)

Thermal overload pickup ..................................................1.20

Motor full-load current (FLA) ............................................1/6 Ict to Ict in steps of 0.1

 

Curve biasing

Phase loss: ....................................................................1.83 x Ir

Phase unbalance: .......................................................1.43 x Ir

Timing accuracy....................................................................

±10% up to 8 x FLA and ±20%

from 8 to 10 x FLA

 

Elements ...................................................................................fault (trip) and warning (alarm)

- warning not valid for ATEX



Phase Loss

Range ........................................................................................fixed at 60% (any phase <40% of max phase)

Accuracy...................................................................................±5%

Time delay................................................................................0–15 seconds in steps of 1s (0 = disable)

immediately when ATEX is selected

 

Timing accuracy.................................................................... ±20%

 

Elements ................................................................................... fault (trip) and warning (alarm)

- warning not valid for ATEX



Current Unbalance

Range.........................................................................................fixed at 30% (any phase <70% of max phase)

Accuracy...................................................................................±5%

Time delay................................................................................0–15 seconds in steps of 1s (0 = disable)

Fix to 500ms when ATEX is selected

 

Timing accuracy....................................................................±20%

 

Elements ...................................................................................fault (trip) and warning (alarm)

 


Ground Fault

Pickup level..............................................................................20–100% of FLA in steps of 10%

Trip time delay band ...........................................................0.1–1.0s in steps of 0.1s

(other values will generate an error)

Timing accuracy....................................................................±20%

 

Elements ...................................................................................fault (trip) and warning (alarm)

 

 