CHAPTER 5: WinESG

EP OS MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL

5.2

2

 

 

Figure 5-13-: WinESG parameterization control panel

Control configuration in illustration A enables and disables the source, defines the sources as local or remote, and defines
the mode of operation of the source (1-bit or 2-bit). Only one source can be set as a remote. The rest, if enabled, will be
automatically set as local.

Profibus DP (PB DP C1):

Profibus class 1 cyclic communication such as PLC, can be set as

1-Bit (level) or 2-Bit (edge), Inverted OFF or Non-Inverted OFF.

1 – Bit:

ON-bit (telegram B10008 bit0 or bit1) will turn the motor ON and OFF.

2-Bit:

ON-bit (telegram B10008 bit0 or bit1) will turn the motor ON and OFF-bit

(telegram B10008 bit0 or bit14) will turn motor off.

Inverted OFF:

active low signal (0) is valid OFF command.

Non-Inverted OFF:

active high signal (1) is valid OFF command.

Remote selection:

selects the remote source – Profibus class 1, Modbus or hardwire

NOTE:

if Profibus Class 1 is enabled it is assigned as a remote.


NOTE:

When changing from 1-bit to 2-bit it is recommended that the power be re-cycled.


NOTE:

If hardwire is set to 1-bit and remote source is hardware it is not recommend to keep remote Off valid,

since it is an invalid combination.

Remote OFF in Local control: valid - Remote source can stop a motor

invalid - Remote source cannot stop a motor