CHAPTER 2: INSTALL ATION/CONFIGURATION

2.6

EP OS MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL

 

 

 

 
 

2.1.2 Electrical installation

 

This section describes the electrical installation of the EntelliPro ES motor relay.

 

 

CAUTION:

EntelliPro ES is not to be used in any way other than described in this manual.

 

 


2.1.2.1 Power supply connection

 

EntelliPro ES3 DP 2 0 and EntelliPro ES5 DP 2 2 are 24Vdc supply input versions, while EntelliPro ES3 DP 3 0,
EntelliPro ES5 DP 3 2, and EntelliPro ES5 DP 3 3 are 110 to 240Vac versions.

 

The operation range for the 24Vdc units is 19Vdc to 29Vdc. The operation range for the 110 to 240Vac units is

77Vac to 266Vac.

 


CAUTION:

Check the voltage rating of the unit before applying control power. Control power outside of the operating

range of the power supply will damage the EntelliPro ES.

 

 

Figure 2-4 shows the EntelliPro wiring connections. Refer to Item A for power supply connections.

 

 

Figure 2‐4: EntelliPro ES wiring connections

 

 

 