7 profibus dp cyclic data, Table 4-12: entellipro es dp input and output data – GE Industrial Solutions EntelliPro ES User Manual

Page 174

Advertising
background image

CHAPTER 4: COMMUNICATION

EP OS MOTOR MANAGEMENT SY STEM – INSTRUCTION MANUAL

4.37

 

 

 

 

 

4.2.7 Profibus DP Cyclic Data

 

The cyclic data is a fast process data transfer between the Profibus DP master and the slave which occurs once
every DP cycle. EntelliPro ES is a modular device supporting up to 144 bytes

of input data and 18 bytes of output

data. Modules define a block size of input and output data to be read by the master, starting from offset zero.
During the network configuration session, modules with varying sizes of input data are provided in the GSD file.

 

Table 4-12 shows the EntelliPro ES cyclic input and output data provided in the GSD file. Refer to section 4.2.10 for
an example of master configuration.

 

 
 

 

EntelliPro ES DP Data Objects

Length

Direction

Data Type

DP V0 (Cyclic)

 

(Byte)

Master

Slave

Input

B 2

Identification telegram

34

<<==

Input

B 2720

Device ID telegram

36

<<==

Output

B 10008

Control telegram

4

==>>

 

Input

B 20008

Status telegram

4

<<==

Input

B 30008

Fault telegram

2

<<==

Input

B 30264

Warning telegram

2

<<==

Input

B 30776

Unit failure telegram

2

<<==

Input

B 2704

Current measurement telegram

24

<<==

Input

B 2705

Fault current telegram

16

<<==

Input

B 2706

Maximum current telegram

16

<<==

Input

B 2707

Switch counter telegram

4

<<==

Input

B 2708

Operating hours telegram

4

<<==

Output

B 2701

Reset telegram

8

 

Input

B 2721

Debug telegram

64

<<==

Output

B 2702

Set telegram

6

 

Input

B 2709

Phase-current L1 telegram

4

<<==

Input

B 2710

Phase-current L2 telegram

4

<<==

Input

B 2711

Phase-current L3 telegram

4

<<==

Input

B 2712

Current average value telegram

4

<<==

Input

B 2713

Earth fault current telegram

4

<<==

Additional Telegrams

not applicable to EntelliPro ES as ESS-DP retrofit

Input

B2734

Additional Counter for V5

43

B400

B40009

4

 

Table 4-12: EntelliPro ES DP Input and output data

<<==

Dynamic Status data Block

==>>

==>>

Inp

ut

B40004

Debug ESSV5

<<==

Inp

ut

2

<<==

2

Advertising