CHAPTER 2: INSTALL ATION/CONFIGURATION

2.62

EP OS MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL

 

 

If Hardwire is selected as a controlling device, one input must be mapped to mode switch local and a different input to
mode switch remote. If input mode switch local is active, all mechanisms defined as locals can control the motor
(ON/OFF). If input mode switch remote is active, the mechanism defined as remote can control the motor (ON/OFF).

If Fixed local is selected as a controlling device, any source assigned as local can control the motor (ON/OFF).

If Fixed remote is selected as a controlling device, only the remote source can control the motor (ON/OFF).

NOTE:

Only one control (local or remote) can be enabled at a time. If both (local and remote) are active the “drawer

ready switch” will be OFF and the motor cannot start.

NOTE:

To make any changes on the configuration, “parameter allowed” must be enabled in WinESG

parameterization/function panel or Modbus function code 6 register 62.

Refer to section 2.2.1 for the motor control detailed configuration.

Pole changer starter operation: when an ON1 command (low speed) is received, contactor K1, controlled by EntelliPro
output relay 41, will close, which will start the motor in a low speed.

When a start function ON2 (high speed) is received contactor K1 opens. When contactor K1 Off status feedback is
received, contactor K2, controlled by EntelliPro output relay 43, closes, which starts the motor in a high speed.

Should an ON2 command (fast start) start be received when K1 is closed, and direct switch over is allowed, K1 will open
immediately, and contactors K2 will close.

Should a start function ON1 be received when K2 is closed, and “allow direct direction switchover” is set, in the WinESG
parameterization\typical settings or Modbus function code 6 register 111 bit3, K2 contactor will open immediately. K1
will close after the “fast to slow wait time” in WinESG parameterization/timer panel or Modbus function code 6 register
30 timer expires