EP OS MOTOR MANAGEMENT SY STEM – INSTRUCTION

MANUAL

Individual configuration of these registers will not give the expected configuration behavior.

NOTE:

Registers 115, 116 and 117 must be programmable sequentially, in order to get the expected configuration.

4.23

CHAPTER 4: COMMUNICATION

 

 

 

 

 

Holding

Register

Modbus

Size

Variable

Description

Min

Max

Step

Units

Scale

Format

Default

113

16 bit

ForceLocalRemote switch

Bit 0: for local switch on Class1 failure.

bit 1 - bit 3: Free

bit 4 - bit 6 : Force local/remote switch to

remote on Modbus Failure

bit 7: Free

Switch setting upon Modbus and/or Profibus

class1 Bus failure

0 = None - Switch remains as is

1 = Local on Profibus Class 1 failure

 

0 - None

1 - Local on Modbus failure

2 - Remote on Modbus failure

3 - OFF

0

127

1

 

 

Unsigned

integer

10

114

16 bit

Protection - Inputs Enable / Disable
bit 0 - Overload

 

bit 1 - Phase LossL

bit 2 - GF

bit 3 - UnbalancedLoad
bit 4 - Thermistor

bit 5 - EmergencyStop
bit 6 - LimitSwitch

bit 7 - SafetyCircuit
bit 8 - MainCircuit

bit 9 - ControlCircuit
bit10 - SwitchPosition

bit 11 - UnderLoadCurrent
bit 12 - OverloadCurrent

bit 13 - ExternalSupervision

bit 14 - CyclicCommunicationLoss
bit 15 - LongStartTime

0 = Disable

1 = Enabled

Example:

If overload protection on holding register 64

is set to failure and this bit is set to 0, then the

overload failure is ignored.

If overload protection on holding register 64

is set to alarm, and this bit is set to 0, then the
overload alarm is ignored.

If overload protection on holding register 64

is set to failure and this bit is set to 1, then the

overload failure is activated.

If overload protection on holding register 64

is set to alarm, and this bit is set to 1, then the
overload alarm is activated.

This is applicable for the Bit 1 thru Bit 15

0

65535

1

 

 

Unsigned

Integer

65471

115

16 bit

Remote Source & Local Remote Switch control

Bit 0 - bit 2

1 - class1

2 - Modbus

3 - Hardwire

 

Bit 4 - bit 6

1 - class1

2 - Modbus

3 - Hardwire

4 - Fixed Local

5 - Fixed Remote

 

Bit0 thru Bit2 defines the Remote source

 

 

 

Bit4 thru Bit6 defines the source that controls
the local/remote switch selection.

 

Note: Fixed local is defined as Hardwire,

Modbus, Profibusand 2

0

127

1

 

 

Unsigned

Integer

34

116

16 bit

Bus Command Configuration

bit 0 - Class1 enable/ disable
bit 1 - Class1 n bit 0r (n+1) bit
bit 2 - level/edge

bit 3 - Inverted OFF / Non-Inverted OFF

 

bit 4 - Class2 Enable/disable
bit 5 - reserved

 

bit 6 - Modbus Enable/disable

Enables the EntelliPro ES controls (ON/OFF/

Reset...) by different protocols

If Profibus DP Class 1 is enabled then bits 1,2,3

must be set per the required operation

 

 

Enables Profibus DP class 2 protocol to control
the motor

 

Enables Modbus protocol to control the motor.

0

127

1

 

 

Unsigned

integer

92

117

16 bit

Hardwire Configuration

Bit 0 - hardwire enable/ disable
bit 1 - hardwire n bit 0r (n+1) bit
bit 2 - hardwire level/edge

Allow EntelliPro ES control via hardware

 

If Bit 0 is enables (2), bit 1 and 2 must be set

0

5

 

 

Unsigned

integer

10244