CHAPTER 3: MOTOR PR OTECTION

EP OS MOTOR MANAGEMENT SY STEM – INSTRUCTION MANUAL

3.15

 

 

 

3.1.5 Overload protection n-times reset

 

EntelliPro ES has an n-times automatic reset function, which allows a defined number of automatic reset operations.
The reset count will be automatically cleared when one hour elapses from the last overload trip.

 

The n-times can be set in the WinESG parameterization/alarm panel shown in the illustration below, or Modbus
function code 6 register 45.

 

Figure 3-11 shows an example of the auto-reset count operation. In this particular example the auto reset is set

to 2.

 
 
 

OL Trip

Auto

Reset 1

OL Trip

Auto

Reset 2

OL Trip

Manual

Reset 1

 

Auto Reset

allowed after

1 hour of last

reset (at -T=3)

 
 

 
 

t = 0

t=1

t=2

t=3

t=n

 

Time (minutes)

 

 

Figure 3-11 EntelliPro Auto-reset operation

 

 

 

For an ATEX configured device, the Auto-Reset parameter can be set to four different values: 0, 1, 2, and 3.

For a non-ATEX configured device, the values allowed are from 0 to 65535. However any value greater than 3 indicates
that Auto-Reset is always allowed.

 

When the auto-reset parameter is set to 0, the auto-reset is disabled and a manual reset is required after an overload
trip.

 