CHAPTER 2: INSTALL ATION/CONFIGURATION

2.22

EP OS MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL

 

 

If Hardwire is selected as a controlling device, one input must be mapped to mode switch local and a different input to
mode switch remote. If input mode switch local is active, all mechanisms defined as locals can control the motor
(ON/OFF). If input mode switch remote is active, the mechanism defined as remote can control the motor (ON/OFF).

If Fixed local is selected as a controlling device, any source assigned as local can control the motor (ON/OFF).

If Fixed remote is selected as a controlling device, only the remote source can control the motor (ON/OFF).

NOTE:

only one control (local or remote) can be enabled at a time. If both (local and remote) are active the “drawer

ready switch” will be OFF and the motor cannot start.

NOTE:

to make any changes on the configuration, “parameter allowed” must be enabled in WinESG

parameterization/function panel or Modbus function code 6 register 62.

Refer to section 2.2.1 for the motor control detailed configuration.

Full-voltage non-reversing starter operation: when an ON1 command is received, contactor K1, controlled by
EntelliPro ES output relay 41, will close, provided the motor is in the off state and the drawer ready switch is active,
which will start the motor. When an OFF command is received contactor K1 will open and the motor will stop.

If the default configuration and the DOL typical are selected in the WinESG parameterization/information panel shown
in the illustration below or by setting Modbus function code 6 register 62 bit0 to 1 and bits 8,9,10 and 11 to 0x0, the
inputs and outputs are mapped as below: