K = cooling factor units = seconds – GE Industrial Solutions EntelliPro ES User Manual

Page 126

Advertising
background image

CHAPTER 3: MOTOR PR OTECTION

3.14

EP OS MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL

 

 

 

 

M otor

Heating

Class 40

K = 1

Class 40

K = 2

Class 40

K = 3

Class 40

K = 4

Class 40

K = 5

Class 40

K = 6

Class 40

K = 7

Class 40

K = 8

Class 40

K = 9

Class 40

K = 10

Class 40

K = 11

Class 40

K = 12

Class 40

K = 13

Class 40

K = 14

Class 40

K = 15

100

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

90

145.8

291.6

437.4

583.2

729

874.8

1020.6

1166.4

1312.2

1458

1603.8

1603.8

1603.8

2041.2

2187

80

307.8

615.6

923.4

1231.2

1539

1846.8

2154.6

2462.4

2770.2

3078

3385.8

3385.8

3385.8

4309.2

4617

70

492.75

985.5

1478.25

1971

2463.75

2956.5

3449.25

3942

4434.75

4927.5

5420.25

5420.25

5420.25

6898.5

7391.25

60

706.05

1412.1

2118.15

2824.2

3530.25

4236.3

4942.35

5648.4

6354.45

7060.5

7766.55

7766.55

7766.55

9884.7

10590.75

50

957.15

1914.3

2871.45

3828.6

4785.75

5742.9

6700.05

7657.2

8614.35

9571.5

10528.65 10528.65 10528.65

13400.1

14357.25

40

1266.3

2532.6

3798.9

5065.2

6331.5

7597.8

8864.1

10130.4

11396.7

12663

13929.3

13929.3

13929.3

17728.2

18994.5

30

1663.2

3326.4

4989.6

6652.8

8316

9979.2

11642.4

13305.6

14968.8

16632

18295.2

18295.2

18295.2

23284.8

24948

20

2223.45

4446.9

6670.35

8893.8

11117.25

13340.7

15564.15

17787.6

20011.05 22234.5 24457.95 24457.95 24457.95

31128.3

33351.75

10

3180.6

6361.2

9541.8

12722.4

15903

19083.6

22264.2

25444.8

28625.4

31806

34986.6

34986.6

34986.6

44528.4

47709

 

Figure 3-10: Thermal cooling model when trip curve is set to IEC class 40.

K = Cooling Factor

Units = seconds