CHAPTER 2: INSTALL ATION/CONFIGURATION

2.28

EP OS MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL

 

 

If the default configuration and the DOL reverse typical are selected in the WinESG parameterization/information shown
in the illustration below or by setting Modbus function code 6 register 62 bit0 to 1 and bits 8,9,10 and 11 to 0x1,the
inputs and outputs are mapped as below:




For EntelliPro ES3 types:

Input 99 is mapped to contactor 1 feedback

- active high

Input 98 is mapped to contactor 2 feedback

- active high

Input 97 is mapped to control circuit feedback

- active low

Input 96 is mapped to main circuit feedback

- active low

Input 95 is mapped to emergency stop

- active low

Input 94 is mapped to external supervision

- active high

Input 93 is mapped to safety circuit

- active low

Output 41 is mapped to contactor 1

Output 43 is mapped to contactor 2

Output 45 is mapped to failure

For EntelliPro ES5 types:

Input 99 is mapped to contactor 1 feedback

- active high

Input 98 is mapped to contactor 2 feedback

- active high

Input 97 is mapped to reset alarm

- active high

Input 96 is mapped to drawer in test mode

- active high

Input 95 is mapped to drawer in operation mode

- active high

Input 94 is mapped to main circuit feedback

- active low

Input 93 is mapped to control circuit

- active low

Input 11 is mapped to command OFF

- active low

Input 12 is mapped to command ON1

- active high

Input 13 is mapped to command ON2

- active high

Input 14 is mapped to external fault

- active high

Input 15 is mapped to external supervision

- active low

Input 16 is mapped to emergency stop

- active low

Input 17 is mapped to safety circuit

- active low

Input 18 is mapped to mode switch local

- active high

Input 19 is mapped to mode switch remote

- active high