K = cooling factor units = seconds – GE Industrial Solutions EntelliPro ES User Manual

Page 123

Advertising
background image

CHAPTER 3: MOTOR PR OTECTION

EP OS MOTOR MANAGEMENT SY STEM – INSTRUCTION MANUAL

3.11

 

 

 

 

M otor

Heating

Class 25

K = 1

Class 25

K = 2

Class 25

K = 3

Class 25

K = 4

Class 25

K = 5

Class 25

K = 6

Class 25

K = 7

Class 25

K = 8

Class 25

K = 9

Class 25

K = 10

Class 25

K = 11

Class 25

K = 12

Class 25

K = 13

Class 25

K = 14

Class 25

K = 15

100

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

90

91.8

183.6

275.4

367.2

459

550.8

642.6

734.4

826.2

918

1009.8

1009.8

1009.8

1285.2

1377

80

193.8

387.6

581.4

775.2

969

1162.8

1356.6

1550.4

1744.2

1938

2131.8

2131.8

2131.8

2713.2

2907

70

310.25

620.5

930.75

1241

1551.25

1861.5

2171.75

2482

2792.25

3102.5

3412.75

3412.75

3412.75

4343.5

4653.75

60

444.55

889.1

1333.65

1778.2

2222.75

2667.3

3111.85

3556.4

4000.95

4445.5

4890.05

4890.05

4890.05

6223.7

6668.25

50

602.65

1205.3

1807.95

2410.6

3013.25

3615.9

4218.55

4821.2

5423.85

6026.5

6629.15

6629.15

6629.15

8437.1

9039.75

40

797.3

1594.6

2391.9

3189.2

3986.5

4783.8

5581.1

6378.4

7175.7

7973

8770.3

8770.3

8770.3

11162.2

11959.5

30

1047.2

2094.4

3141.6

4188.8

5236

6283.2

7330.4

8377.6

9424.8

10472

11519.2

11519.2

11519.2

14660.8

15708

20

1399.95

2799.9

4199.85

5599.8

6999.75

8399.7

9799.65

11199.6

12599.55 13999.5 15399.45 15399.45 15399.45

19599.3

20999.25

10

2002.6

4005.2

6007.8

8010.4

10013

12015.6

14018.2

16020.8

18023.4

20026

22028.6

22028.6

22028.6

28036.4

30039

 

Figure 3-7: Thermal cooling model when trip curve is set to IEC class 25.

 

 

K = Cooling Factor

Units = seconds

Advertising