4.26

EP OS MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL

CHAPTER 4: COMMUNICATION

 

 

 

 

 

Holding

Register

Modbus

Size

Variable

Description

Min

Max

Step

Units

Scale

Format

Default

126

16 bit

Digital Output - Motor Relay 41

 

Note:

One of the three motor contact relay output

must be mapped as a contactor (value 1
thru 5).

When any motor contact relay is mapped as

a contact then the rest of the output relays
can be treated as a signal output and set to
any value.

Signal output can be dual mapped (first byte
mapped to operation1, and 2nd byte mapped
to a different operation)

Example of mapping output 3 as a signal

output relay

Identification Feedback Status = 23 (first

byte)

Main Contactor 2 Feedback Status

Flashing = 38 (second byte)

 

Convert 3823 to HEX = 0x0EEF.

Convert 0x0EEF to decimal - 3823

Place 3823 in the output 3 register

 

Note: second byte has the highest priority

when both are present

1 = Main Contactor 1 / Breaker ON / Slow

Contactor

2 = Main Contactor 2 / Breaker OFF / Fast

Contactor

3 = Start Contactor 3 / by pass Connector

4 = Delta Contactor 4

5 = Redundancy Contactor

6 = Main Contactor 1 Feedback Status

7 = Main Contactor 2 Feedback Status

8 = ESS_DP_Parameter_Mode

9 = Switch_Protected_Status

10 = Start_Attempt_Status

11 = Drawer_Ready_Status

12 = General Warning Status

13 = General Fault Status

14 = Safety Circuitry Status

15 = Local Switch Status

16 = Remote Switch Status

17 = Drawer test Mode Status

18 = Drawer operation Mode Status

19 = Limit Switch 1 Status

20 = Limit Switch 2 Status

21 = General Device Error Status

22 = Identification Feedback Status

23 = Class1 Failure

24 = Modbus Failure

25 = By Pass Contactor Switched ON Status

26 = Switching 1 progress Status

27 = Switching 2 progress Status

28 = Breaker Tripped2 Status

29 = Charger Status

30 = Torque Switching 1 Status

31 = Torque Switching 2 Status

32 = Start Phase Status

33 = Run Phase Status

34 = Thermistore Line Broken Status

35 = Thermistor Line Shorted Status

36 = Main Contactor 1 Feedback Status

37 = Main Contactor 2 Feedback Status

Flashing

38 = ESS_DP_Parameter_mode

39 = Switch_protected_Status Flashing

40 = Start_Attempt_Status Flashing,

41 = D

rawer_Ready_Status Flashing,

42 = General Warning Status Flashing

43 = General Fault Status Flashing

44 = Safety Circuitry Status Flashing

45 = Local Switch Status Flashing

46 = Remote Switch Status Flashing

47 = Drawer test Mode Status Flashing

48 = Drawer operation Mode Status Flashing

49 = Limit Switch 1 Status Flashing

50 = Limit Switch 2 Status Flashing

51 = General Device Error Status Flashing

52 = Identification Feedback Status Flashing

53 = Class1 Failure Flashing

54 = Modbus Failure Flashing

55 = By Pass Contactor Switched ON Status

Flashing

56 = Switching 1 progress Status Flashing

57 = Switching 2 progress Status Flashing

58 = Breaker Tripped2 Status Flashing

59 = Charger Status Flashing

60 = Torque Switching 1 Status Flashing

61 = Torque Switching 2 Status Flashing

62 = Start Phase Status Flashing

63 = Run Phase Status Flashing

64 = Thermistore Line Broken Status Flashing

65 = Thermistor Line Shorted Status Flashing

66 = DIGITALOUTPUT4 / Soft Stop Relay

67 = DIGITALOUTPUT5 / Soft Start External

Fault

68 = Digital Output 6,

69 = Digital Output 7

70 = Digital Output 8

1

71

1

 

 

Unsigned

Integer

9

127

16 bit

Digital Output - Motor Relay 43

See Digital Output 0 for configuration and

setting (Holding register 126)

1

71

1

 

 

Unsigned

Integer

7

128

16 bit

Digital Output - Motor Relay 45

See Digital Output 0 for configuration and

setting (Holding register 126)

1

71

1

 

 

Unsigned

Integer

7

129

16 bit

Digital Output - Signal Relay 22

See Digital Output 0 for configuration and

setting (Holding register 126)

1

71

1

 

 

Unsigned

Integer

7